American Power Conversion 7500/10000 VA user manual Terminal Mode to Configure UPS Parameters

Page 14

Terminal Mode to Configure UPS Parameters

Terminal Mode is a menu driven interface that enables enhanced configuration of the UPS. Connect the serial cable to the serial port on the back of the UPS.

When using PowerChute® Network Shutdown software:

1.Open a terminal program. Example: HyperTerminal

From the Desktop, go to Start => Programs => Accessories => Communication =>HyperTerminal.

2.Double-click on the HyperTerminal icon.

Follow the prompts to choose a name and select an icon. Disregard the message, “...must install a modem,” if it is displayed. Click OK.

Select the COM port that is connected to your UPS. The port settings are:

bits per second - 2400 data - bits 8

parity - none stop bit - 1

flow control - none

Click Enter

3.Example for setting the number of external battery packs (SURT192XLBP):

Once the blank terminal window is open, follow these steps to enter the number of battery packs:

Press ENTER to initiate terminal mode. Press ENTER multiple times, until the prompt User Name: is displayed. Follow the prompts. Type slowly, waiting until each character appears on the screen prior to typing the next character.

Web/SNMP Card defaults:

User Name: apc

Password: apc

Press 1 and ENTER to select Device Manager.

Select the model by entering the corresponding number, then press ENTER.

Press 3 and ENTER to select Configuration.

Press 1 and ENTER to select Battery.

Press 2 and ENTER to change the Battery Settings.

Type in the number of external battery packs (four battery modules per pack), then press ENTER. (Number of packs: 1= internal battery module, 2 = 1 SURT192XLBP, 3 = 2 SURT192XLBP, etc.)

Press 3 and ENTER to accept the changes.

Press ESC multiple times (5) to return to the main menu.

Press 4 and ENTER to log out.

12

Image 14
Contents APC Smart-UPSRT Page Unpacking PlacementIntroduction Removing the BatteriesHardwiring XLT, XLJ, and Xltw ModelsXLT/XLJ/XLTW Models Page L6-20 L6-30 250V 20A 250V 30A Serial Port Operation On Battery Operation Affect the voltage displayUser Configurable Items Models EPO Emergency Power Off Option Adhere to national and local electrical codes when wiringTerminal Mode to Configure UPS Parameters Transporting the UPS Replacing the Battery ModulesStorage Troubleshooting Replace Battery LED flashes Service Contacting APCRegulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V ModelsDeclaration of Conformity Limited Warranty