USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
Automatic | Every 14 days | Every 7 days(168 hours), | Set the interval at which the | |
| (336 hours) | 14 days (336 hours) | UPS will execute a | |
|
| On Startup Only, |
| |
|
| No |
| |
|
|
|
| |
UPS ID | UPS_IDEN | Up to eight characters to | Uniquely identify the UPS, (i.e. | |
|
| define the UPS | server name or location) for | |
|
|
| network management purposes. | |
|
|
|
| |
Date of Last Battery | Manufacture Date | Date of | Reset this date when you replace | |
Replacement |
| Battery Replacement | the battery modules. | |
|
| mm/dd/yy |
| |
|
|
|
| |
Minimum Capacity | 0 percent | 0, 15, 25, 35, 50, 60, 75, | Following a | |
Before Return from |
| 90 percent | shutdown, the battery modules | |
Shutdown |
|
| will be charged to the specified | |
|
|
| percentage before powering | |
|
|
| connected equipment. | |
|
|
|
| |
Alarm Delay After | 5 second delay | 5 or 30 second delay | Mute ongoing alarms or disable | |
Line Failure |
| At Low Battery | all alarms permanently. | |
|
| Never |
| |
|
|
|
| |
Shutdown Delay | 20 seconds | 0, 20, 60, 120, 240, 480, | Set the interval between the time | |
|
| 720, 960 seconds | when the UPS receives a | |
|
|
| shutdown command and the | |
|
|
| actual shutdown. | |
|
|
|
| |
Duration of | 2 minutes | 2, 5, 7, 10, 12, 15, 18, | The low battery warning beeps | |
Low Battery Warning. | PowerChute | 20 minutes | are continuous when two | |
|
| minutes of run time remain. | ||
| software provides |
| ||
| automatic, |
| Change the warning interval | |
| unattended |
| default to a higher setting if the | |
| shutdown when |
| operating system requires a | |
| approximately 2 |
| longer interval for shutdown. | |
| minutes of battery |
|
| |
| operated runtime |
|
| |
| remains. |
|
| |
|
|
|
| |
Synchronized | 0 seconds | 0, 20, 60, 120, 240, 480, | The UPS will wait the specified | |
Delay |
| 720, 960 seconds | time after the return of utility | |
|
|
| power before | |
|
|
| branch circuit overload). | |
|
|
|
| |
High Bypass Point | +10% of | +5%, +10%, +15%, | Maximum voltage that the UPS | |
| output voltage | +20% | will pass to connected | |
| setting |
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
|
| 8 |
|