American Power Conversion RT user manual Wiring and Connecting the UPS

Page 4

Wiring and Connecting the UPS

5000/6000 VA XLI MODELS ONLY: HARDWIRING INSTRUCTIONS

Wiring must be performed by a qualified electrician.

Install a high magnetic 30/32 A utility circuit breaker.

Adhere to all national and local electrical codes.

Use #10 AWG gauge (5 mm2) wire.

1.Switch the utility circuit breaker OFF.

2.Remove the input access panel.

3.Remove circular knockout.

4.Run #10 AWG gauge (5 mm2) wire through the access panel, and connect the wires to the terminal block (green: ground, brown: hot, blue: neutral). Use an appropriate strain relief (not included).

5.Switch the utility circuit breaker ON.

6.Check line voltages.

7.Replace the access panel.

2

Image 4
Contents APC Smart-UPSRT Page Introduction SpecificationsUnpacking Wiring and Connecting the UPS Connecting the Battery Modules and Attaching the Front Bezel Normal bypass Avoid using extension cords Operation On Battery Operation Does not affect the voltage displayUser Configurable Items XLJ models VA models 5000/6000 VA models Replacing the Battery Module Disconnecting the Battery for Transport TROUBLESHOOTING, SERVICE, and Warranty Information Bypass LED Illuminates Service Limited WarrantyRegulatory Agency Approvals and Radio Frequency Warnings 200, 208, 220, 230, 240 V ModelsDeclaration of Conformity APC Worldwide Customer Support