NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OPTIONAL SMART SLOT ACCESSORY CARDS OR TERMINAL MODE.
FUNCTION | FACTORY | USER SELECTABLE | DESCRIPTION | |
DEFAULT | CHOICES | |||
|
| |||
Low Bypass Point | Minimum voltage that the UPS | |||
| voltage setting |
| will pass to connected | |
|
|
| equipment during internal | |
|
|
| bypass operation. | |
|
|
|
| |
Output Voltage | XLJ models: | XLJ models: | Allows the user to select the | |
| 200 VAC | 200 VAC | UPS output voltage while | |
| XLT models: | XLT models: | online. | |
| 208 VAC | 200, 208, 220, 230, |
| |
|
| 240 VAC |
| |
| XLI models: | XLI models: |
| |
| 230 VAC | 200, 208, 220, 230, |
| |
|
| 240 VAC |
| |
| XLTW models: | XLT/XLTW models: |
| |
| 220 V | 200, 208, 220, 230, |
| |
| 240 VAC |
| ||
|
|
| ||
|
|
|
| |
Output Frequency | Automatic | 50 ± 3 Hz | Sets the allowable UPS output | |
| 50 ± 3 Hz or | 50 ± 0.1 Hz | frequency. Whenever possible, | |
| 60 ± 3 Hz | the output frequency tracks the | ||
| 60 ± 3 Hz | |||
| 60 ± 0.1 Hz | input frequency. | ||
|
| |||
|
|
|
| |
Number of | 1 | Number of Connected | Defines the number of internal | |
Battery Packs |
| Internal Battery Packs, | and external connected battery | |
|
| (two modules per pack) | packs for proper run time | |
|
|
| prediction. | |
|
|
|
|
CONNECTING THE EPO (EMERGENCY POWER OFF) OPTION
The output power can be disabled in an emergency by closing a switch connected to the EPO.
Adhere to National and local electrical codes when wiring the EPO.
EPO switch
The EPO switch is internally powered by the UPS for use with
The EPO circuit is considered a Class 2 circuit, (UL, CSA standards) and a SELV circuit (IEC standard).
9