4:USER CONFIGURABLE ITEMS

NOTE: SETTINGS ARE ADJUSTED THROUGH POWERCHUTE SOFTWARE

 

FUNCTION

 

 

FACTORY

 

 

USER SELECTABLE

 

 

DESCRIPTION

 

 

 

 

 

 

 

 

 

 

 

 

DEFAULT

 

 

CHOICES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Self-Test

 

Every 14 days

 

Every 7 days

 

Set the interval at which the UPS will

 

 

 

 

(336 hours)

 

(168 hours),

 

execute a self-test.

 

 

 

 

 

 

 

Every 14 days

 

 

 

 

 

 

 

 

 

 

(336 hours),

 

 

 

 

 

 

 

 

 

 

On Startup Only,

 

 

 

 

 

 

 

 

 

 

No Self-Test

 

 

 

 

 

 

 

 

 

 

 

 

UPS ID

 

UPS_IDEN

 

Up to eight charac-

 

Uniquely identify the UPS, (i.e. server

 

 

 

 

 

 

 

ters (alphanumeric)

 

name or location) for network man-

 

 

 

 

 

 

 

 

 

 

agement purposes.

 

 

 

 

 

 

 

 

 

Date of Last

 

Manufacture Date

 

mm/dd/yy

 

Reset this date when you replace the

 

Battery

 

 

 

 

 

 

 

battery module.

 

Replacement

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Minimum Capacity

 

0 percent

 

0, 15, 50, 90 percent

 

Specify the percentage to which batter-

 

Before Return from

 

 

 

 

 

 

 

ies will be charged following a low-

 

Shutdown

 

 

 

 

 

 

 

battery shutdown before powering

 

 

 

 

 

 

 

 

 

 

connected equipment.

 

 

 

 

 

 

 

 

 

Voltage Sensitivity

 

High

 

High sensitivity,

 

Note: In situations of poor power qual-

 

The UPS detects

 

 

 

 

Medium sensitivity,

 

ity, the UPS may frequently transfer to

 

 

 

 

 

Low sensitivity

 

battery operation. If the connected

 

and reacts to line

 

 

 

 

 

 

 

 

 

 

 

 

 

equipment can operate normally under

 

voltage distortions

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

such conditions, reduce the sensitivity

 

by transferring to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

setting to conserve battery capacity

 

battery operation to

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

and service life.

 

protect connected

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

equipment.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alarm Delay After

 

5 seconds

 

5 second delay,

 

Set the delay to avoid alarms for minor

 

Line Fail

 

 

 

 

30 second delay,

 

power glitches.

 

 

 

 

 

 

 

At low battery

 

 

 

 

 

 

 

 

 

 

condition,

 

 

 

 

 

 

 

 

 

 

No alarm

 

 

 

 

 

 

 

 

 

 

 

 

Shutdown Delay

 

60 seconds

60, 180, 300, 600

 

 

Set the interval between the time when

 

 

 

 

 

 

 

seconds

 

the UPS receives a shutdown com-

 

 

 

 

 

 

 

 

 

 

mand and the actual shutdown.

 

 

 

 

 

 

 

 

 

 

 

 

7

Image 9
Contents APC Smart-UPSSC Page Introduction UnpackPosition the UPS Tower Configuration Mount the UPS in a Two-Post Rack Reinstall battery, battery bracket, and screws Connect the UPS to the Network if Applicable Connect Equipment to the UPSStart the UPS Front Display Panel User Configurable Items 110/120 V model Storage Battery ReplacementTROUBLESHOOTING, SHIPPING, and Service Replace BATTERY/BATTERY Disconnected LED is Illuminated Shipping and Service Regulatory and Warranty Information Limited Warranty