| PROBLEM AND POSSIBLE |
| SOLUTION | |||
|
| CAUSE |
|
| ||
THE OVERLOAD LED IS LIT AND THE UPS EMITS A SUSTAINED ALARM TONE | ||||||
The UPS is overloaded. |
| The connected equipment exceeds the specified “maximum load” as de- | ||||
|
|
|
|
|
| fined in Specifications at the APC web site, www.apc.com. |
|
|
|
|
|
| The alarm remains on until the overload is removed. Disconnect nonessen- |
|
|
|
|
|
| tial equipment from the UPS to eliminate the overload. |
|
|
|
|
|
| The UPS continues to supply power as long as it is online and the circuit |
|
|
|
|
|
| breaker does not trip; the UPS will not provide power from batteries in the |
|
|
|
|
|
| event of a utility voltage interruption. |
|
|
|
|
|
| If a continuous overload occurs while the UPS is on battery, the unit turns |
|
|
|
|
|
| off output in order to protect the UPS from possible damage. |
|
|
|
|
|
|
|
THE REPLACE BATTERY LED IS LIT |
| |||||
Replace Battery LED flashes |
| Check that the battery connectors are fully engaged. | ||||
and short beep is emitted every |
|
| ||||
two seconds to indicate the |
|
| ||||
battery is disconnected. |
|
| ||||
Weak battery. |
| Allow the battery to recharge for 24 hours. Then, perform a | ||||
|
|
|
|
|
| problem persists after recharging, replace the battery. |
Failure of a battery |
| The UPS emits short beeps for one minute and the replace battery LED | ||||
|
|
|
|
|
| illuminates. The UPS repeats the alarm every five hours. Perform the self- |
|
|
|
|
|
| test procedure after the battery has charged for 24 hours to confirm the |
|
|
|
|
|
| replace battery condition. The alarm stops and the LED clears if the bat- |
|
|
|
|
|
| tery passes the |
|
|
|
|
|
| |
THE SITE WIRING FAULT LED IS LIT | ||||||
The site wiring LED is lit |
|
|
| The UPS is plugged into an improperly wired utility power outlet. Wiring | ||
|
|
| faults detected include missing ground, | |||
| ||||||
(rear panel). |
| overloaded neutral circuit. Contact a qualified electrician to correct the | ||||
120V models only. |
| building wiring. | ||||
|
|
|
| |||
THE INPUT CIRCUIT BREAKER TRIPS | ||||||
The plunger on the circuit |
| Reduce the load on the UPS by unplugging equipment and press the | ||||
breaker (located above the input |
| plunger in. | ||||
cable connection) pops out. |
|
| ||||
|
|
|
| |||
|
| |||||
AVR BOOST OR AVR TRIM LEDS LIGHT | ||||||
AVR Boost or Trim LEDs light |
| Have qualified service personnel check your facility for electrical prob- | ||||
Your system is experiencing |
| lems. If the problem continues, contact the utility company for further | ||||
| assistance. | |||||
excessive periods of low r high |
| |||||
|
| |||||
voltage. |
|
| ||||
|
|
|
|
|
|
|
12