3:USER CONFIGURABLE ITEMS
NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT
ACCESSORY CARDS.
FUNCTION |
| FACTORY |
| USER SELECTABLE CHOICES | DESCRIPTION | |||
| DEFAULT |
| ||||||
|
|
|
|
|
|
|
| |
Automatic |
| Every 14 days |
| Every 7 days | This function sets the inter- | |||
| (336 hours) |
| (168 hours), |
| val at which the UPS will | |||
|
|
|
| On Startup Only, No Self- | execute a | |||
|
|
|
| Test |
| your software manual for | ||
|
|
|
|
|
| details. |
| |
|
|
|
|
|
|
| ||
UPS ID | UPS_IDEN |
| Up to eight characters to | Use this field to uniquely | ||||
|
|
|
| define the UPS | identify the UPS, (ie. server | |||
|
|
|
|
|
| name or location) for net- | ||
|
|
|
|
|
| work management purposes. | ||
|
|
|
|
|
|
| ||
Date of Last Battery Re- | Manufacture |
| Date of Battery Replacement | Reset this date when you | ||||
placement | Date |
| mm/dd/yy |
| replace the battery module. | |||
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| ||
Minimum Capacity Be- | 0 percent |
| 15, 30, 45, 50, 60, 75, 90 | The UPS will charge its | ||||
fore Return from Shut- |
|
|
| percent |
| batteries to the specified | ||
down |
|
|
|
|
| percentage before return | ||
|
|
|
|
|
| from a shutdown. | ||
|
|
|
|
|
| |||
Voltage Sensitivity |
|
|
| Brightly lit: UPS is set to | To change the UPS sensitiv- | |||
|
| |||||||
The UPS detects and |
|
|
| high sensitivity (default). | ity, press the voltage sensi- | |||
|
|
|
|
| tivity button |
| (rear panel). | |
reacts to line voltage |
|
|
| Dimly lit: | UPS is set to |
| ||
|
|
| Use a pointed object (such as | |||||
distortions by transferring |
|
|
| medium sensitivity. | ||||
|
|
| a pen) to do so. |
| ||||
to battery operation to |
|
|
| Off: | Low battery |
| ||
|
|
|
|
|
| |||
protect the connected |
|
|
| You can change the sensitiv- | ||||
|
| |||||||
equipment. Where power |
|
|
| warning interval is about | ity level through Power- | |||
quality is poor, the UPS |
|
|
| eight minutes. | Chute software. |
| ||
may frequently transfer to |
|
|
|
|
|
|
|
|
battery operation. If the |
|
|
|
|
|
|
|
|
connected equipment can |
|
|
|
|
|
|
|
|
operate normally under |
|
|
|
|
|
|
|
|
such conditions, reduce |
|
|
|
|
|
|
|
|
the sensitivity setting to |
|
|
|
|
|
|
|
|
conserve battery capacity |
|
|
|
|
|
|
|
|
and service life. |
|
|
|
|
|
|
|
|
|
|
|
|
| ||||
Alarm Control | Enable |
| Mute, Disable | User can mute an ongoing | ||||
|
|
|
|
|
| alarm or disable all existing | ||
|
|
|
|
|
| alarms permanently. | ||
|
|
|
|
| ||||
Shutdown Delay | 90 seconds |
| 0, 180, 270, 360, 450, 540, | Sets the interval between the | ||||
|
|
|
| 630 seconds |
| time when the UPS receives | ||
|
|
|
|
|
| a shutdown command and | ||
|
|
|
|
|
| actual shutdown. | ||
|
|
|
|
|
|
|
|
|
|
|