APC UPS user manual Off

Page 9

NOTE: SETTINGS ARE MADE THROUGH SUPPLIED POWERCHUTE SOFTWARE OR OPTIONAL SMART SLOT

ACCESSORY CARDS.

FUNCTION

 

FACTORY

USER SELECTABLE CHOICES

DESCRIPTION

 

DEFAULT

 

 

 

 

 

 

 

Low Battery Warning.

 

 

 

Brightly lit: Low battery

The low battery warning

 

 

 

PowerChute interface

 

 

 

warning interval is about two

beeps are continuous when

 

 

 

minutes.

 

two minutes of run time

software provides auto-

 

 

 

 

 

 

 

Dimly lit:

Low battery

remain.

matic, unattended shut-

 

 

 

 

 

 

warning interval is about five

 

 

 

down when approxi-

 

 

 

To change the warning in-

 

 

 

minutes.

 

mately two minutes (by

 

 

 

 

terval default setting, press

 

 

 

Off:

Low battery

 

 

 

default) of battery oper-

 

 

 

the voltage sensitivity button

 

 

 

warning interval is about

ated run time remains.

 

 

 

(use a pointed object such as

 

 

 

eight minutes.

 

 

 

 

a pen to do so), while press-

 

 

 

 

Possible interval settings:

 

 

 

 

ing and holding the

 

 

 

 

 

 

2, 5, 8, 11, 14, 17, 20, 23

 

 

 

 

 

 

 

 

 

 

 

minutes.

 

button (front panel).

 

 

 

 

Synchronized Turn-on

0 seconds

60, 120, 180, 240, 300, 360,

The UPS will wait the speci-

Delay

 

 

 

420 seconds

fied time after the return of

 

 

 

 

 

 

utility power before turn-on

 

 

 

 

 

 

(to avoid branch circuit

 

 

 

 

 

 

overload).

 

 

 

 

High Transfer Point

230V models:

230V models:

To avoid unnecessary bat-

 

253VAC

257, 261, 265VAC

tery usage, set the high

 

120V models:

120V models:

transfer point higher if the

 

utility voltage is chronically

 

127VAC

130, 133, 136VAC

 

high and the connected

 

 

 

 

 

 

 

100V models:

100V models:

equipment is known to work

 

108VAC

110, 112, 114VAC

under this condition.

 

 

 

 

Low Transfer Point

230V models:

230V models:

Set the low transfer point

 

208VAC

196, 200, 204VAC

lower if the utility voltage is

 

120V models:

120V models:

chronically low and the con-

 

nected equipment can toler-

 

106VAC

97, 100, 103VAC

 

ate this condition.

 

 

 

 

 

 

 

100V models:

100V models:

 

 

 

 

92VAC

86, 88, 90VAC

 

 

 

 

 

 

 

Output Voltage

230V models:

230V models:

230V models ONLY, allow

 

230VAC

220, 240VAC

the user to select the output

 

 

 

 

 

 

voltage.

 

 

 

 

 

 

 

 

 

7

Image 9
Contents APC Smart-UPS Page Introduction UnpackingPositioning the UPS Plug in the battery connector n Connecting Equipment and Power to the UPSPower management software and interface kits can be used Operation On Battery Operation User Configurable Items Off Storage Replacing the Battery Module1500VA Model Disconnecting the Battery for Transport Troubleshooting 120V models only Utility Voltage Contacting APC Service230V Models Regulatory Agency Approvals and Radio Frequency WarningsDeclaration of Conformity Limited Warranty