American Power Conversion 5000RMB user manual On-Battery Run Time

Page 18

On-Battery Run Time

Note:

UPS battery life differs based on usage and environment.

APC recommends that the battery/batteries be changed once every two years.

Typical On-Battery Run Time Versus Load, in Hours

Load (VA)

Run Time (hours)

 

 

100

7.17

 

 

150

5.95

 

 

200

5.04

 

 

300

3.88

 

 

400

2.96

 

 

500

2.37

 

 

600

1.92

 

 

800

1.40

1000

1.06

 

 

1200

0.83

 

 

1400

0.65

 

 

1600

0.54

 

 

2000

0.39

 

 

2200

0.33

 

 

2500

0.26

 

 

3000

0.19

 

 

3500

0.16

 

 

4000

0.13

 

 

4500

0.11

 

 

5000

0.09

 

 

12

Image 18
Contents 990-7080C 03/2005 990-7080C 03/2005 Handling Safety Electrical SafetyReplacement and Recycling of Batteries Page Table of Contents Page Introduction ContentsHow to Unpack the SU 5000 UPS UnpackingInstalling the SU5000RMB InstallationPlacement Position the UPSLeft Front Connect Input Power to the UPS Vac UnitsVac Units with Line Cord Vac Units for Hard Wire Install PowerChute and Accessories Install the BatteriesPower up the UPS and Accessories Connect Equipment to the UPSInitial Startup Operating Instructions SmartTrim Low Battery Overload SmartBoostReplacing the Battery Battery Replacement ProcedureStorage Conditions User Configuration ItemsStorage Extended storageOn-Battery Run Time Specifications Troubleshooting Problem and Possible Cause Solution UPS will not turn onService Limited WarrantyAPC Contact Information 200/208 Vac Units Vac UnitsRadio Frequency Interference Appendix B Transporting Your Smart-UPS