User Configuration Items
Note: Setting these items requires optional software or hardware.
Function | Factory | User Selectable | Description |
| Default | Choices |
|
Automatic | Every 14 | Every 7 days (168 | Sets the interval at which the UPS will |
| days | hours), On Startup | execute a |
| (336 hours) | Only, No |
|
UPS ID | UPS_IDEN | Up to eight characters | Use this field to uniquely identify the UPS |
|
| to define the UPS. | for network management purposes. |
|
|
|
|
Date of Last Battery | Manufacture | Date of Battery | Reset this date on battery replacement. |
Replacement | Date | Replacement |
|
|
|
|
|
Minimum Capacity Before | 0 percent | 15, 50, 90 percent | The UPS will charge its batteries to the |
Return from Shutdown |
|
| specified percentage before return from a |
|
|
| shutdown. |
|
|
|
|
Sensitivity | Normal | Reduced, Low | Set lower than normal sensitivity to avoid |
|
|
| lowered battery capacity and service life in |
|
|
| situations where the load can tolerate minor |
|
|
| power disturbances. |
Duration of Low Battery | 2 minutes | 5, 7, 10 minutes | Sets the time before shutdown at which the |
Warning |
|
| UPS issues a low battery warning. Set |
|
|
| higher than the default only if the OS needs |
|
|
| the time for graceful shutdown. |
Alarm Delay After Line | 5 second | 30 second delay, At | To avoid alarms for minor power glitches, |
Fail | delay | Low Battery | set the alarm delay. |
|
| Condition, No Alarm |
|
Shutdown Delay | 20 seconds | 180, 300, 600 seconds | Sets the interval between when the UPS |
|
|
| receives a shutdown command and when |
|
|
| shutdown occurs. |
|
|
|
|
Synchronized | 0 seconds | 60, 180, 300 seconds | To avoid branch circuit overload, the UPS |
Delay |
|
| will wait the specified time after the return |
|
|
| of utility power before |
|
|
|
|
High Transfer Point | 253 | 264, 271, 280 | To avoid unnecessary battery usage, set the |
|
|
| High Transfer Point higher if the utility |
|
|
| voltage is chronically high and the load is |
|
|
| known to work well under this condition. |
|
|
|
|
Low Transfer Point | 196 | 188, 204, 208 | Set the Low Transfer Point lower if the |
|
|
| utility voltage is chronically low and the |
|
|
| load can tolerate this condition. |
|
|
|
|
Storage
Storage Conditions
Store the UPS covered and upright in a cool, dry location, with its battery disconnected.