American Power Conversion 5000UXI user manual Battery Charge and Run Times

Page 16

Battery Charge and Run Times

Note:

UPS battery life differs based on usage and environment.

The tables below show both the time required for charging UPS and battery pack batteries for rated protection and typical run times.

Note:

The SU5000UXI is designed for use with the UXBP48M or equivalent 48 Volt battery pack.

Typical Maximum Recharge Times (In Hours) To 90% Of Rated Capacity

Number of Battery Packs

Recharge Time

Number of Battery Packs

Recharge Time

1

5

6

18

 

 

 

 

2

8

7

20.5

 

 

 

 

3

10.5

8

23

 

 

 

 

4

13

9

25.5

 

 

 

 

5

15.5

10

28

 

 

 

 

SU5000UXI Typical On-battery Run Times

Load VA

With 1

With 2

With 3

With 4

With 5

With 6

 

battery pack

battery packs

battery packs

battery packs

battery packs

battery packs

 

 

 

 

 

 

 

1000

4.3

9.0

14.5

20.0

25.0

30.0

 

 

 

 

 

 

 

2000

2.1

4.8

7.5

9.9

12.5

15.0

 

 

 

 

 

 

 

3000

1.2

2.4

3.6

4.8

6.0

7.2

4000

0.5

1.4

2.3

3.2

4.0

4.8

 

 

 

 

 

 

 

5000

0.3

0.8

1.4

2.0

2.5

3.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Image 16
Contents 990-7082A REV4 7/01 990-7082A REV4 7/01 Handling Safety Electrical SafetyPage Table of Contents Page Installation IntroductionUnpacking Position the UPSHardwire the Electrical Connection Input Cable Output CableConnect Power to the UPS Connect the External BatteriesInstall PowerChute and Accessories Click on Configuration Click on UPS Operating ParametersStep To see the change in number of external battery packs Initial Startup Operating Instructions Low Battery Load Bar GraphOverload SmartTrimStorage User Configuration ItemsStorage Conditions Battery Charge and Run Times UPS battery life differs based on usage and environmentTroubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact Information