Page 8

2. Hardwire the Electrical Connection

Caution:

The electrical connection must be made by an authorized electrician according to national and local regulations.

Verify that the supply line contains a 25 Ampere circuit breaker BEFORE hardwiring the UPS.

Ensure that the batteries are not installed in the UPS until the hardwiring is complete.

Incorporate a readily accessible disconnect device in the fixed wiring design.

1.Select the appropriate wire size and connectors. For most applications, #10 AWG (5 sq. mm) wire should be sufficient.

2.The input and output wiring terminals are located on the rear panel of the UPS. Remove the hardwire cover ￿ by unscrewing the single screw ￿ that holds it in place.

￿

￿

 

 

￿

3.

Use a screwdriver to loosen the Strain clamp ￿.

 

 

 

4.

Feed the input wire cable through the strain clamp on the left side and feed the output wire cable through the

 

strain clamp on the right side.

 

 

 

 

5.

Use a knife or pliers to strip off the plastic on the end of the cable to expose the copper wire. Strip all six wires.

6.

Use a flathead screwdriver to connect the wires to the terminal block inside the UPS. Loosen the screw, then

 

feed the copper wire into the terminal block and tighten the screw. Make sure the terminal block is wired from

 

left to right as shown in the following table:

 

 

 

 

 

 

 

 

 

 

 

Input Cable

Input Cable

Input Cable

Output Cable

Output Cable

Output Cable

 

Black (Hot)

White (Neutral)

Green (Ground)

Green (Ground)

Black (Hot)

White (Neutral)

 

 

 

 

 

 

 

7.

Once all the wires are connected to the terminal block, verify consistency of colors on the top and bottom of the

 

terminal block.

 

 

 

 

 

8.

Inspect the connections and location of the excess wires before tightening the strain clamp.

 

9.

Using a screwdriver tighten the strain clamp securing the cables.

 

 

10. Replace the hardwire cover and fasten with the screw (removed in step 2).

2

Image 8
Contents 990-7082A REV4 7/01 990-7082A REV4 7/01 Handling Safety Electrical SafetyPage Table of Contents Page Installation IntroductionUnpacking Position the UPSHardwire the Electrical Connection Input Cable Output CableConnect Power to the UPS Connect the External BatteriesInstall PowerChute and Accessories Click on Configuration Click on UPS Operating ParametersStep To see the change in number of external battery packs Initial Startup Operating Instructions Low Battery Load Bar GraphOverload SmartTrimStorage Conditions User Configuration ItemsStorage Battery Charge and Run Times UPS battery life differs based on usage and environmentTroubleshooting Service Limited WarrantyIf the UPS requires service do not return it to the dealer APC Contact Information