3:OPERATING THE SMART-UPSWITH A BATTERY PACK

SETTING THE SMART-UPSTO RECOGNIZE THE BATTERY PACK(S)

Smart-UPS XL models cannot determine how many external battery packs are connected to them. You must program the Smart-UPS XL with the appropriate number of external batteries in one of four ways using:

nSmart-UPS Battery Pack Utility (BATTPACK)

nPowerChute® plus Version 5.x for Windows 95, Windows 98, Windows NT

nTerminal Program to Change the Number of External Battery Packs

nHyperTerminal Program to Change the Number of External Battery Packs

Each method is described in this section.

It is important to follow these instructions. The number of batteries affects the run time calculations the Smart-UPS performs when it is running on battery power.

USING THE SMART-UPS BATTERY PACK UTILITY (BATTPACK)

You can use the BATTPACK program with DOS or at a Microsoft® Windows DOS prompt. BATT- PACK cannot be used with a DOS emulator or VDM (virtual DOS machine) like those in Windows 95, Windows 98, or Windows NT.

You must use the APC UPS Link cable to communicate to the UPS. Use either of two black cables: part numbers 940-0024C or 940-1524C.

At the DOS prompt, type: battpack com[X] [Y]

where [X] represents the available serial port the Battery Pack Utility uses to access the Smart-UPS. [Y] represents the number of external battery packs.

In the following example, the black cable is attached to communication port 1. There are four exter- nal battery packs. The program confirms that the update is successful.

C:> battpack com1 4

USING POWERCHUTE® PLUS VERSION 5.X FOR WINDOWS 95, WINDOWS 98, WINDOWS NT

PowerChute plus 5.x for Windows NT is compatible with NT 3.5.1 SP5, NT 4.0 Workstation (at least SP1), or NT 4.0 Server (at least SP1).

1.Install the software per the instructions on the CD. After rebooting the computer, access the Pow- erChute plus graphical user interface.

2.Click on Configuration.

3.Click on UPS Operating Parameters.

4.Adjust the External Battery Pack field to the appropriate number of external battery packs.

5.Click OK.

9

Image 11
Contents APC Smart-UPS Page Safety Information Battery Safety Location sturdy enough to handle the weight Installing the Battery PackReviewing Connectors on the Battery Pack Cleat into its groove and slide the battery pack UPS Œ Connecting a Battery Pack to Another Battery Pack Page Click on Configuration Click on UPS Operating Parameters Operating the SMART-UPSWITH a Battery PackTo see the number of external packs. a new unit will display Storage and Replacement Page Service Refer to the information provided at the APC Internet site Contact and Warranty Information