American Power Conversion 480kW400V manual Press On the keyboard until

Page 13

Stop/Start UPS and Operating the External Service Bypass

Action

Steps 1-4 apply to all the parallel systems. Note that this will switch all systems into bypass operation

1.

Press

on the keyboard

Display shows

 

2.

Press

or

on the keyboard until

Bypass operation

 

 

 

 

: NO

3.

Press

on the keyboard

Bypass operation

 

 

 

 

: YES

4.

Press

on the keyboard

 

All systems switch to bypass operation

Do not switch off any of the UPS systems until steps 5-8 have been completed

5. Check light indication on the bypass panel

Bypass operation

Lamp indication on Bypass Panel

Green light (H003) above the bypass switch handle (Q003) lights up

6.

Set the external bypass switch (Q003) to position 1

Green light (H004)

 

 

above the output switch

 

 

handle (Q004) and green

 

 

lights (H002) above the

 

 

output switch handles

 

 

(Q002) light up

7.

Set the output switch (Q004) to position 0

H003 switches off

 

 

H002 and H004 still on

8.

Set all output switches (Q002) to position 0

H002 and H004 still on

9.Open the front door of any one system and press the green ON and the red OFF button simultaneously

The acoustic alarm sounds for 30 secs* Repeat for (all) other system(s)

10.Set all input switches (Q001) to position 0

The red alarm LED below the display lights up and the acoustic alarm sounds for 30 secs*

Display shows

**System OFF**

*Reset the acoustic alarm by pressing the key.

 

990-4058

 

 

User Guide APC Silcon 480kW 400V UPS

13

Image 13
Contents Copyright 2001 APC Japan 480kW400V UPS User GuideThank You User Guide APC Silcon 480kW 400V UPSIntroduction IntroductionDisplay Unit Stop UPS for stand-by Stop/Start UPS and Operating the External Service BypassStart UPS from stand-by Switching off the UPS Stop UPS for complete power downSystem OFF UPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Using the Remote DisplayEconomy Mode Parameter Settings Parameter SettingsParameter Settings Programming Keys Switching to Bypass OperationProgramming Example To return to normal operation Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsAlarms Description Action Possible AlarmsAlarms and Events Parallel Operation Alarms Rectifying Alarm MessagesCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkHow to Contact APC