American Power Conversion 480kW400V manual Parameter Settings

Page 21

Parameter Settings

4.0 Parameter Settings

Below tables show operating parameters programmable from keyboard. Only qualified users should alter programming parameters. See below examples.

Parameter Settings

Parameter

Setting*

 

Comments

 

 

 

 

 

 

 

 

Bypass operation

YES, NO

YES will switch the system into

 

 

bypass mode***

 

 

 

 

 

 

 

 

Language

GB, D, F, DK, S, SF, NL, PL, CZ,

Languages of text in display

 

E, P, SK, H

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Autostart

YES, NO

Automatic restart by mains return

 

 

(1 min. delay). Ensures quick

 

 

battery recharge.

 

 

 

 

 

 

 

 

Remote shutdown active

YES, NO

Shutdown of UPS by remote

 

 

signal when in battery operation.

 

 

Saves battery energy.

 

 

 

 

 

 

 

 

Remote shutdown

HIGH, LOW

Nature of remote shutdown

 

 

signal level

 

 

 

 

 

 

 

 

 

 

 

Remote shutdown time

0, 1, 2, 3, 4, 5, 6, 7, 8, 9, 10 min.

Time delay on remote shutdown

 

 

of UPS

 

 

 

 

 

 

 

 

 

 

 

Battery capacity test

Initiates back-up time check.

 

 

Time measured from start until it

 

 

reaches low DC warning level

 

 

(See User Guide, section 6).

 

 

 

 

 

 

 

Battery monitor test **

Initiates checks of battery

 

 

condition by 25% discharging.

 

 

 

 

 

 

 

Automatic battery test**

OFF, 3,6 months

Activates the battery monitor test

 

 

in cyclic intervals.

 

 

 

 

 

 

 

 

 

 

Battery monitor reset**

Press the

 

 

and

 

 

key to

 

 

 

 

 

reset alarm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(flashing light).

 

 

 

 

 

 

 

 

 

 

 

Boost charge

YES, NO

YES results in boost charge (10

 

 

hours)

 

 

 

 

 

 

 

 

 

 

 

Autoboost charge

YES, NO

YES results in boost charge after

 

 

battery operation (10 hours).

 

 

 

 

 

 

 

 

Enter new date

YYMMDD

Set to local date

 

 

 

 

 

 

 

 

Enter new time

HHMMSS

Set to local time (24 hour clock)

 

 

 

 

 

 

 

 

 

*Factory settings in bold

**For systems with active Battery Monitor only

***Do not leave system running in bypass mode (Static bypass) for extended periods of time, as batteries are not recharged in bypass mode.

990-4058

User Guide APC Silcon 480kW 400V UPS

21

Image 21
Contents Copyright 2001 APC Japan 480kW400V UPS User GuideThank You User Guide APC Silcon 480kW 400V UPSIntroduction IntroductionDisplay Unit Stop/Start UPS and Operating the External Service Bypass Stop UPS for stand-byStart UPS from stand-by Switching off the UPS Stop UPS for complete power downSystem OFF UPS start-up Start UPS from complete power downSystem start-up now completed Bypassing the Single System UPS Operating the External Service Bypass Switch single systemsStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Operation OperationKeyboard Display of Measured Values Using the Remote DisplayEconomy Mode Parameter Settings Parameter SettingsParameter Settings Switching to Bypass Operation Programming KeysProgramming Example To return to normal operation Alarms and Events Alarms and EventsDisplaying the Alarm Stack Mode CommentsAlarms Description Action Possible AlarmsAlarms and Events Rectifying Alarm Messages Parallel Operation AlarmsCorrection of false alarm situations during service Maintenance & Testing Maintenance & TestingBattery Monitoring Test Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored Warranty WarrantyAPC Silcon UPS Limited Factory Warranty How to Contact APC How to Contact APCAPC Corporate APC DenmarkHow to Contact APC