American Power Conversion 480kW400V manual Alarms and Events

Page 26

Alarms and Events

 

Alarms

Description

Action

 

 

 

 

23.

Main inverter failure

Temperature of main inverter, too

Check fan, check for airflow

 

 

high or inverter fuse blown

obstructions, check for overload,

 

 

 

check fuse

 

 

 

 

24.

High temperature of delta

Temperature of delta inverter, too

Check fan, check for airflow

 

inverter

high

obstructions, check for overload

 

 

 

 

25.

Low DC shutdown

Battery discharged to minimum

Ensure battery recharging

 

 

permissible level

 

 

 

 

 

26.

Low DC warning

Battery nearly discharged

Save your data now

 

 

 

 

27.

Mains momentarily outside

Short disturbances on mains

 

tolerance

supply (1 ms transients)

 

 

 

 

 

28.

Mains outside tolerance

Mains input voltage R.M.S. value

 

 

outside tolerance

 

 

 

 

 

29.

Mains frequency outside

Mains input frequency outside

 

tolerance

tolerance

 

 

 

 

 

30.

Bypass momentarily outside

Short disturbances on bypass

 

tolerance

voltage

 

 

 

 

 

31.

Bypass outside tolerance

Bypass input voltage outside

 

 

tolerance

 

 

 

 

 

32.

Bypass frequency outside

Bypass input frequency outside

 

tolerance

tolerance

 

 

 

 

 

33.

Output momentarily outside

Short disturbance on output

If message reappears -

 

tolerance

voltage (inrush current)

call for assistance

 

 

 

 

34.

Output outside tolerance

Output voltage outside tolerance

Call for assistance

 

 

 

 

35.

Output frequency outside

Output frequency outside

Call for assistance

 

tolerance

tolerance

 

 

 

 

 

36.

High battery temperature

Battery ambient temperature too

Check system ambient

 

 

high

temperature, check fan, check for

 

 

 

airflow obstructions

 

 

 

 

37.

Battery weak

Battery capacity below 75% or

Test battery capacity

 

 

battery MCCB/fuse switched off

 

 

 

 

 

38.

Battery defective

Insufficient battery capacity or

Call for assistance

 

 

battery MCCB/fuse switched off

 

 

 

 

 

39.

System locked in operation

UPS has made 10 attempts within

Unlock.

 

mode

1 minute to switch from bypass to

If message reappears -

 

 

battery operation, or “High DC

call for assistance

 

 

warning” has appeared 10-20

 

 

 

times within 1 minute

 

 

 

 

 

40.

RAM1 memory write error

UPS fault

Call for assistance

 

 

 

 

41.

Memory write error

UPS fault

Call for assistance

 

 

 

 

42.

Communication to VQ bypass

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

43.

Communication to VQ output

UPS fault

Call for assistance

 

lost

 

 

 

 

 

 

44.

Communication to DMU lost

UPS fault

Call for assistance

 

 

 

 

45.

Communication to controller

UPS fault.

Call for assistance

 

lost

Display will show invalid UPS data

 

 

 

 

 

990-4058

26

User Guide APC Silcon 480kW 400V UPS

Image 26
Contents 480kW400V UPS User Guide Copyright 2001 APC JapanUser Guide APC Silcon 480kW 400V UPS Thank YouDisplay Unit IntroductionIntroduction Start UPS from stand-by Stop/Start UPS and Operating the External Service BypassStop UPS for stand-by Stop UPS for complete power down Switching off the UPSSystem OFF Start UPS from complete power down UPS start-upSystem start-up now completed Operating the External Service Bypass Switch single systems Bypassing the Single System UPSStop/Start UPS and Operating the External Service Bypass System OFF Normal operation Load power 0% Bypass operation Bypassing the Parallel UPS System All UPSs Press On the keyboard until Stop/Start UPS and Operating the External Service Bypass Set input switches Q001 to position Isolating one UPS in a Parallel/Redundant System Stop/Start UPS and Operating the External Service Bypass Keyboard OperationOperation Using the Remote Display Display of Measured ValuesEconomy Mode Parameter Settings Parameter SettingsParameter Settings Programming Example Switching to Bypass OperationProgramming Keys To return to normal operation Displaying the Alarm Stack Alarms and EventsAlarms and Events Mode CommentsPossible Alarms Alarms Description ActionAlarms and Events Correction of false alarm situations during service Rectifying Alarm MessagesParallel Operation Alarms Battery Monitoring Test Maintenance & TestingMaintenance & Testing Battery Capacity TestUntil Battery capacity Test Xxx Press Data stored APC Silcon UPS Limited Factory Warranty WarrantyWarranty APC Corporate How to Contact APCHow to Contact APC APC DenmarkHow to Contact APC