Alarms and Events
5.3Possible Alarms
| Alarms | Description | Action |
|
|
| |
1. Peak current limiter active | Peak current limiter activated and | Check for blown fuses in | |
|
| UPS switched to bypass operation. | installation |
|
| System overload |
|
|
|
| |
2. Bypass power supply fault | Fault in redundant PSU for bypass. | Call for assistance | |
|
| UPS still 100% able to operate in |
|
|
| all modes. |
|
|
|
| |
3. Delta current limiter active | Input current limiter activated and | Check for overload. | |
|
| UPS switched to bypass operation | If message is repetitive - |
|
|
| call for assistance |
|
|
| |
4. Faulty fan | Blocked or faulty fan | Remove blocking or replace fan | |
|
|
| |
5. High DC warning | Switching off big output load | If alarm is repeated, reduce load | |
|
|
| change |
|
|
| |
6. High DC shutdown | UPS fault | Call for assistance | |
|
|
| |
7. | Off button or emergency power | – | |
|
| shut down activated |
|
|
|
| |
8. Synchronization error | UPS unable to synchronize with | Check if phase rotation of mains | |
|
| input frequency | input voltage is correct. If OK, call |
|
|
| for assistance |
|
|
| |
9. Inverter voltage error | Inverter average voltage outside | – | |
|
| limits (normal message during |
|
|
| system |
|
|
|
|
|
10. | Parallel synchronization | Parallel UPS unable to | Check external parallel cables - |
| error | synchronize | call for assistance |
|
|
|
|
11. | Inverter current limiter active | Inverter overload | Reduce UPS output load |
|
|
|
|
12. | Overload. Load exceeding | UPS overload | Reduce UPS output load |
| 100% |
|
|
|
|
|
|
13. | Second power supply fault | UPS fault | Call for assistance |
|
| (only systems > 160kW) |
|
|
|
|
|
14. | Internal power supply fault | UPS fault. Only bypass operation | Call for assistance |
|
| possible |
|
|
|
|
|
15. | Battery MCCB is off | Battery MCCB/fuse not closed or | Close MCCB / insert new fuse. If |
|
| released | released again - |
|
|
| call for assistance. |
|
|
|
|
16. | **Q004 off** | Output switch position for UPS in | – |
|
| parallel |
|
|
|
|
|
17. | **Q003 off** | External bypass switch position | – |
|
|
|
|
18. | **Q002 off** | UPS output switch position | – |
|
|
|
|
19. | **Q001 off** | UPS input switch position | – |
|
|
|
|
20. | High temperature of isolation | Temperature of isolation input/ | Check fan, check for airflow |
| transformer | output transformer, too high | obstructions, check for overload |
|
|
| |
21. High temperature of main static | Temperature of static input switch, | Check fan, check for airflow | |
| switch | too high | obstructions, check for overload |
|
|
|
|
22. | High temperature of bypass | Temperature of static bypass | Check fan, check for airflow |
| static switch | switch, too high | obstructions, check for overload |
|
|
|
|
User Guide APC Silcon 480kW 400V UPS | 25 |