APC SMX2000RMLV2U Troubleshooting, UPS emits an audible beeping sound at long intervals

Page 16

Troubleshooting

Problem and Possible Cause

Solution

 

The UPS will not turn on or there is no output

 

 

The unit has not been turned on.

Press the ON button to turn on the UPS.

 

 

The UPS is not connected to utility

Ensure that the power cable is securely connected to the unit and to the utility

power.

power supply.

 

 

There is an internal UPS fault.

Do not attempt to use the UPS. Unplug the UPS and have it serviced

 

immediately.

The UPS is operating on battery, while connected to input utility power

There is very high, very low, or distorted input line voltage or frequency.

Move the UPS to a different outlet on a different circuit. Test the input voltage with the utility voltage display. If acceptable to the connected equipment, reduce the UPS sensitivity.

Test the utility input power to ensure the unit is receiving input power.

UPS emits an audible beeping sound at long intervals

The UPS is in normal operation.

The UPS is protecting the connected equipment. See the display interface to view the status of the UPS.

UPS does not provide expected backup time

The UPS battery is weak due to a recent outage or is near the end of its service life.

Charge the battery. Batteries require recharging after extended outages and wear out faster when put into service often or when operated at elevated temperatures. If the battery is near the end of its service life, consider replacing the battery even if the replace battery indicator is not yet illuminated.

The UPS is overloaded.Check the UPS load display. Unplug unnecessary equipment, such as printers.

The Fault indicator is lit and the UPS displays a fault message and emits a constant beeping sound

Internal UPS fault.

Do not attempt to use the UPS. Turn the UPS off and have it serviced

 

immediately.

The replace battery indicator is illuminated

The battery has a weak charge.

Allow the battery to recharge for at least four hours. Then, perform a self-test. If the problem persists after recharging, replace the battery.

The replacement battery is not properly

Ensure that the battery connector is securely connected.

connected.

 

The display interface has a Site Wiring Fault message

Wiring faults detected include missing ground, hot-neutral polarity reversal, and overloaded neutral circuit.

If the UPS indicates a site wiring fault, have a qualified electrician inspect the building wiring. (Applicable for Low Voltage (120 V) units only.)

14

Smart-UPS X 2000/2200/3000 VA

Image 16
Contents Smart-UPSX Page Safety OverviewAbout the UPS Product OverviewSpecifications Environmental SpecificationsRear panel Operating ConditionsInstallation Network Management Card External Battery PackConnect Equipment to the UPS OperationBasic Connections Using the display interface Display InterfaceOverview Menu OverviewSmart-UPS X 2000/2200/3000 VA About Configuration UPS SettingsStart-up Settings Function Factory Default Options DescriptionGeneral Settings Audible Alarm Interval SettingReset to Factory No DefaultUsing the Switched Outlet Groups Switched Outlet GroupsCustomize the Switched Outlet Groups Network Management Card Settings Emergency Power Off EPO OverviewNormally open contacts Normally closed contactsTroubleshooting UPS does not provide expected backup timeReplace battery indicator is illuminated Display interface has a Site Wiring Fault messageService Service and SupportTransport the unit Smart-UPS Factory Warranty Page APC Worldwide Customer Support 990-3651C 09/2011