CONSTANT VOLTAGE (CV) TESTS
CV Setup. For all CV tests set the output current at full rated output to assure CV operation. The onset of constant current can cause a drop in output voltage, increased ripple, and other performance changes not properly ascribed to the con- stant voltage operation of the supply.
Load Regulation (Load Effect)
Definition: CV Load regulation is the change in the steady state value of dc output voltage due to a change in load resis- tance from open circuit to full load or from full load to open cir- cuit.
Test Parameters:
Measured Variable: Output Voltage
Expected Results: Less than 0.01% plus 2 mV
Test Procedure:
a.Connect the test equipment as shown in Figure
b.Turn the supply's power on and turn CURRENT con- trol fully clockwise.
c.Turn up output voltage to the full rated value (8 V for E3614A, 20 V for E3615A, 35 V for E3616A and 60 V for E3617A) as read on the digital voltmeter.
d.Record the output voltage at the digital voltmeter.
e.Operate the electronic load in open(input off) mode.
f.When the reading settles, record the output voltage on the digital voltmeter again. Check that the two recorded readings differ less than 0.01% of output voltage plus 2 mV.
MASTER |
|
| LOCAL |
|
|
| POWER SUPPLY | |
|
|
|
|
| UNDER TEST | |||
|
|
|
|
|
|
|
| |
M/S 1 | M/S 2 | CV |
| CC | SENSE |
|
| |
SLAVE |
|
| REMOTE |
|
|
|
| |
| + | - |
| + | - | + | - |
|
+S | OUT |
| CV |
| CC | VREF A1 | A2 A3 A4 A5 | |
|
|
|
|
|
|
| + | DIGITAL |
|
|
|
|
|
|
|
| |
|
|
|
|
|
|
| - | VOLTMETER |
|
|
|
| - |
|
|
| |
|
|
|
|
|
|
|
| |
|
|
| Rs | TO |
|
|
|
|
|
|
| DVM |
|
|
| ||
|
|
|
|
|
|
| ||
|
|
|
| + |
|
| Model | Rs |
|
|
|
|
|
|
| ||
- |
| + |
|
|
| E3614A, 15A, 16A | 0.1 ohm 0.1% 10W | |
|
|
|
|
|
| |||
ELECTRONIC |
|
|
| E3617A | 1 ohm 1% 5W | |||
| LOAD |
|
|
|
|
|
|
Figure A-4. Basic Test Setup
Line Regulation (Source Effect)
Definition: Line regulation is the change in the steady state value of dc output voltage due to a change in ac input voltage from a minimum to a maximum value(±10% of nominal volt- age).
Test Parameter:
Measured Variable: Output Voltage
Expected Results: Less than 0.01% plus 2 mV
Test Procedure:
a.Connect the test equipment as shown in Figure
b.Connect the supply to the ac power line through a variable autotransformer which is set for low line volt- age(104 Vac for nominal 115 Vac, 90 Vac for nominal 100 Vac, and 207 Vac for nominal 230 Vac).
c.Turn the supply's power on and turn CURRENT con- trol fully clockwise.
d.Adjust VOLTAGE control until the front panel VOLTS display indicates exactly the maximum rated output voltage.
e.Record voltage indicated on the digital voltmeter.
f.Adjust autotransformer to high line voltage(127 Vac for nominal 115 Vac, 110 Vac for nominal 100 Vac, and 253 Vac for nominal 230 Vac).
g.When the reading settles, record the output voltage again. Check that the two recorded readings differ less than 0.01% of output voltage plus 2 mV.
Load Transient Response Time
Definition : This is the time for the output voltage to return to within a specified band around its voltage following a change from full load to half load or half load to full load.
Test Parameter:
Measured Variable: Output Voltage Transients
Expected Results: Less than 50 usec (at 15 mV from base line)
Test Procedure:
a.Connect the test equipment as shown in Figure
b.Turn the supply's power on and turn CURRENT con- trol fully clockwise.
c.Turn up output voltage to the full rated value.
d.Set the electronic load to transient operation mode between one half of supply's full rated value and sup- ply's full rated value at a 1 KHz rate with 50% duty cycle.
e.Set the oscilloscope for ac coupling, internal sync and lock on either the positive or negative load transient.
f.Adjust the oscilloscope to display transients as in Fig- ure
g.Check that the pulse width of the transients at 15 mV from the base line is no more than 50 usec as shown.