Agilent Technologies E3616A, E3614A, E3617A Constant Voltage CV Tests, Load Regulation Load Effect

Page 18

CONSTANT VOLTAGE (CV) TESTS

CV Setup. For all CV tests set the output current at full rated output to assure CV operation. The onset of constant current can cause a drop in output voltage, increased ripple, and other performance changes not properly ascribed to the con- stant voltage operation of the supply.

Load Regulation (Load Effect)

Definition: CV Load regulation is the change in the steady state value of dc output voltage due to a change in load resis- tance from open circuit to full load or from full load to open cir- cuit.

Test Parameters:

Measured Variable: Output Voltage

Expected Results: Less than 0.01% plus 2 mV

Test Procedure:

a.Connect the test equipment as shown in Figure A-4. Operate the electronic load in constant current mode and set its current to the full rated value of the power supply (6 A for E3614A, 3 A for E3615A, 1.7 A for E3616A and 1 A for E3617A).

b.Turn the supply's power on and turn CURRENT con- trol fully clockwise.

c.Turn up output voltage to the full rated value (8 V for E3614A, 20 V for E3615A, 35 V for E3616A and 60 V for E3617A) as read on the digital voltmeter.

d.Record the output voltage at the digital voltmeter.

e.Operate the electronic load in open(input off) mode.

f.When the reading settles, record the output voltage on the digital voltmeter again. Check that the two recorded readings differ less than 0.01% of output voltage plus 2 mV.

MASTER

 

 

LOCAL

 

 

 

POWER SUPPLY

 

 

 

 

 

UNDER TEST

 

 

 

 

 

 

 

 

M/S 1

M/S 2

CV

 

CC

SENSE

 

 

SLAVE

 

 

REMOTE

 

 

 

 

 

+

-

 

+

-

+

-

 

+S

OUT

 

-S

CV

 

CC

VREF A1

A2 A3 A4 A5

 

 

 

 

 

 

 

+

DIGITAL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

-

VOLTMETER

 

 

 

 

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Rs

TO

 

 

 

 

 

 

 

DVM

 

 

 

 

 

 

 

 

 

 

 

 

 

 

+

 

 

Model

Rs

 

 

 

 

 

 

 

-

 

+

 

 

 

E3614A, 15A, 16A

0.1 ohm 0.1% 10W

 

 

 

 

 

 

ELECTRONIC

 

 

 

E3617A

1 ohm 1% 5W

 

LOAD

 

 

 

 

 

 

Figure A-4. Basic Test Setup

Line Regulation (Source Effect)

Definition: Line regulation is the change in the steady state value of dc output voltage due to a change in ac input voltage from a minimum to a maximum value(±10% of nominal volt- age).

Test Parameter:

Measured Variable: Output Voltage

Expected Results: Less than 0.01% plus 2 mV

Test Procedure:

a.Connect the test equipment as shown in Figure A-4. Operate the electronic load in constant current mode and set its current to the full rated value of the power supply.

b.Connect the supply to the ac power line through a variable autotransformer which is set for low line volt- age(104 Vac for nominal 115 Vac, 90 Vac for nominal 100 Vac, and 207 Vac for nominal 230 Vac).

c.Turn the supply's power on and turn CURRENT con- trol fully clockwise.

d.Adjust VOLTAGE control until the front panel VOLTS display indicates exactly the maximum rated output voltage.

e.Record voltage indicated on the digital voltmeter.

f.Adjust autotransformer to high line voltage(127 Vac for nominal 115 Vac, 110 Vac for nominal 100 Vac, and 253 Vac for nominal 230 Vac).

g.When the reading settles, record the output voltage again. Check that the two recorded readings differ less than 0.01% of output voltage plus 2 mV.

Load Transient Response Time

Definition : This is the time for the output voltage to return to within a specified band around its voltage following a change from full load to half load or half load to full load.

Test Parameter:

Measured Variable: Output Voltage Transients

Expected Results: Less than 50 usec (at 15 mV from base line)

Test Procedure:

a.Connect the test equipment as shown in Figure A-4, but replace the DVM with the oscilloscope. Operate the electronic load in constant current mode.

b.Turn the supply's power on and turn CURRENT con- trol fully clockwise.

c.Turn up output voltage to the full rated value.

d.Set the electronic load to transient operation mode between one half of supply's full rated value and sup- ply's full rated value at a 1 KHz rate with 50% duty cycle.

e.Set the oscilloscope for ac coupling, internal sync and lock on either the positive or negative load transient.

f.Adjust the oscilloscope to display transients as in Fig- ure A-5.

g.Check that the pulse width of the transients at 15 mV from the base line is no more than 50 usec as shown.

A-4

Image 18
Contents Agilent E361xA 60W Bench Series DC Power Supplies AprilSafety Summary Operating Instructions General Information Temperature Coefficient Operating Temperature RangeMeter Programming Resolution Line FuseInput Power Requirements InstallationInstallation Data Initial InspectionTURN-ON Checkout Procedure Power CordOperating Instructions Operating Modes Local Operating ModeConnecting Loads Operation Beyond Rated OutputRemote Operating Modes Remote Voltage SensingRemote Analog Voltage Programming MULTIPLE-SUPPLY Operation Normal Parallel OperationAUTO-PARALLEL Operation Normal Series Operation Gramming according to the remote-programming instructionsAUTO-SERIES Operation Total output voltage to ground must not exceed 240 VdcAUTO-TRACKING Operaton = slave output voltageLoad Considerations Service Information Maintenance Test Equipment RequiredOperation Verification Tests Type Required Characteristics USE Recommended Model Performance TestsMeasurement Techniques Line Regulation Source Effect Constant Voltage CV TestsLoad Regulation Load Effect Load Transient Response TimePARDRipple and Noise Pardrms MeasurementPARDPeak-to-Peak Measurement Constant Current CC Tests CV Drift StabilityAdjustment and Calibration Procedure CC Drift StabilityReference and Bias Circuit TroubleshootingOverall Troubleshooting Procedure Regulating Loop TroublesSymptom Checks and Probable Causes Overvoltage Protection Circuit TroublesStep Action Response Probable Cause Step Measure Response Probable Cause Replaceable Parts Table A-10. Replaceable Parts List Table A-10. Replaceable Parts List Contd R28,111 0698-3228 Resistor 49.9K +-1% .125W TF TC=0+-100 RESISTOR-VAR 10K +-10% ALL IC V RGLTR-FXD-POS 4.8/5.2V TO-220 PKG ALL DIODE-GEN PRP 180V 200MA DO-35 ALL Table A-11. Component Value Model Page Page Page Page Manual Supplement Constant Voltage Mode T EAlternative Voltage Programming Using Resistors Programming Voltage Common to the Minus OutputProgramming Voltage Common to the Minus Output Constant Current Mode Constant Current with Voltage ProgrammingCurrent Monitoring Remote Resistor Programming Connections Remote Resistor Programming, Constant VoltageRemote Resistor Programming, Constant Current Certification Declaration of Conformity