Agilent Technologies E3615A Operating Instructions, TURN-ON Checkout Procedure, Power Cord

Page 7

e.Replace the cover and mark the supply clearly with a tag or label indicating the correct line voltage and fuse that is in use.

Figure 2. Line Voltage Selector (set for 115 Vac)

Power Cord

To protect operating personnel, the instrument should be grounded. This instrument is equipped with a three conductor power cord. The third conductor is the ground conductor and when the power cord is plugged into an appropriate receptacle, the supply is grounded.

The power supply was shipped with a power cord for the type of outlet used at your location. If the appropriate cord was not included, contact your nearest Agilent Sales Office to obtain the correct cord.

OPERATING INSTRUCTIONS

INTRODUCTION

This section explains the operating controls and indicators and provides information on many operating modes possible with your instrument. The front panel controls and indicators are illustrated in Figure 3.

Figure 3. Front-Panel Controls and Indicators

1.LINE Switch: Pressing this switch turns the supply on, or off.

2.VOLTAGE Control: Clockwise rotation increases output volt- age.

3.CURRENT Control: Clockwise rotation increases output cur- rent.

4.DISPLAY OVP/CC SET Switch: Pressing this switch causes the VOLTS display to show voltage setting for overvoltage shutdown (trip voltage) and the AMPS display to show the current control set value. Setting values are either front panel settings or remote voltage programmed settings.

5.OVP Adjust Screwdriver Control: While pressing the DIS- PLAY OVP/CC SET switch, rotating the control clock-wise with a small, flat-blade screwdriver increases the setting for overvoltage shutdown.

6.VOLTS Display: Digital display of actual output voltage, or OVP shutdown setting.

7.AMPS Display: Digital display of actual output current, or output-current setting.

8.CV LED Indicator: Output voltage is regulated when lighted. This means the power supply is operating in the constant volt- age mode.

9.CC LED Indicator: Output current is regulated when lighted. This means the power supply is operating in the constant cur-

rent mode.

10.OVP LED Indicator: Output is shutdown by the occurrence of an overvoltage when lighted. Removing the cause of over- voltage and turning the power off, then on, resets the power supply.

TURN-ON CHECKOUT PROCEDURE

The following checkout procedure describes the use of the front panel controls and indicators illustrated in Figure 3 and ensures that the supply is operational:

MASTER

 

LOCAL

 

+

_

 

+

_

+

_

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

M/S1

M/S2

CV

CC

SENSE

 

OUT

-S

CV

 

CC

VREF A1

A2

A3

A4

A5

 

 

 

 

+S

 

 

SLAVE

 

REMOTE

 

 

 

 

 

 

 

 

 

 

 

 

Figure 4. Switch Settings of Rear-Panel Control for Turn-

On Checkout

a.Disconnect power cord.

b.Check that the rear-panel switch settings are as shown in Fig- ure 4.

c.Check that the rear panel label indicates that the supply is set to match your input line voltage (If not, refer to "Line Voltage Option Conversion".).

d.Check that the fuse on the rear panel is correct for your line voltage.

e.Connect the power cord and push the LINE switch to ON.

f.While pressing OVP/CC SET switch, verify that the OVP shutdown is set above 8.0, 20.0, 35.0, or 60.0 Vdc for E3614A, E3615A, E3616A, or E3617A respectively. If not, turn up OVP Adjust with a small flat-blade screwdriver.

g.Turn VOLTAGE control fully counter clockwise to ensure that the output of VOLTS display decreases to 0 Vdc, then fully clockwise to ensure that output voltage increases to the maxi- mum output voltage.

h.While pressing OVP/CC SET switch, turn the CURRENT con- trol fully counter clockwise and then fully clockwise to ensure

1-7

Image 7
Contents April Agilent E361xA 60W Bench Series DC Power SuppliesSafety Summary Operating Instructions General Information Line Fuse Operating Temperature RangeMeter Programming Resolution Temperature CoefficientInitial Inspection InstallationInstallation Data Input Power RequirementsPower Cord TURN-ON Checkout ProcedureOperating Instructions Operation Beyond Rated Output Local Operating ModeConnecting Loads Operating ModesRemote Voltage Sensing Remote Operating ModesRemote Analog Voltage Programming Normal Parallel Operation MULTIPLE-SUPPLY OperationAUTO-PARALLEL Operation Gramming according to the remote-programming instructions Normal Series OperationTotal output voltage to ground must not exceed 240 Vdc AUTO-SERIES Operation= slave output voltage AUTO-TRACKING OperatonLoad Considerations Service Information Test Equipment Required MaintenanceOperation Verification Tests Performance Tests Type Required Characteristics USE Recommended ModelMeasurement Techniques Load Transient Response Time Constant Voltage CV TestsLoad Regulation Load Effect Line Regulation Source EffectPardrms Measurement PARDRipple and NoisePARDPeak-to-Peak Measurement CV Drift Stability Constant Current CC TestsCC Drift Stability Adjustment and Calibration ProcedureRegulating Loop Troubles TroubleshootingOverall Troubleshooting Procedure Reference and Bias CircuitOvervoltage Protection Circuit Troubles Symptom Checks and Probable CausesStep Action Response Probable Cause Step Measure Response Probable Cause Replaceable Parts Table A-10. Replaceable Parts List Table A-10. Replaceable Parts List Contd R28,111 0698-3228 Resistor 49.9K +-1% .125W TF TC=0+-100 RESISTOR-VAR 10K +-10% ALL IC V RGLTR-FXD-POS 4.8/5.2V TO-220 PKG ALL DIODE-GEN PRP 180V 200MA DO-35 ALL Table A-11. Component Value Model Page Page Page Page Manual Supplement T E Constant Voltage ModeProgramming Voltage Common to the Minus Output Alternative Voltage Programming Using ResistorsProgramming Voltage Common to the Minus Output Constant Current with Voltage Programming Constant Current ModeCurrent Monitoring Remote Resistor Programming, Constant Voltage Remote Resistor Programming ConnectionsRemote Resistor Programming, Constant Current Certification Declaration of Conformity