ENGINEERING DATA

LATENT RECOVERY/MOISTURE TRANSFER CORE

The cross-flow energy recovery core transfers heat and water vapour between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS - Each air stream has one centrifugal blower driven by a common PSC motor. 5 speed fan operation. High speed - 120 VAC, 182 Watts.

FILTERS - Washable air filters in exhaust and supply air streams.

MOUNTING THE ERV - Four threaded inserts at corners of case designed to accept four PVC reinforced polyester straps that are supplied with the unit.

DEFROST - Damper defrost system.

CASE - Twenty gauge prepainted galvanized steel (G60) for superior corrosion resistance. Insulated to prevent exterior condensation.

DRAIN CONNECTIONS - Two - 1/2” (12mm) O.D.

CONTROLS - ControlAir 15

WEIGHT 63 lbs. (28.7 kg) SHIPPING WEIGHT 65 lbs. (29.6 kg)

Model 200ERVD

PERFORMANCE

Net supply airflow in cfm (L/s) against external static pressure

E.S.P

cfm

L/s

@ 0.1” (25 Pa)

214

(101)

@ 0.2” (50 Pa)

206

(97)

@ 0.3” (75 Pa)

193

(91)

@ 0.4” (100 Pa)

184

(87)

@ 0.5” (125 Pa)

170

(80)

Sensible Effectiveness

67%

@127cfm (60 L/s) (CSA C439M)

 

Sensible Efficiency 32°F (0°C)

60%

Total Efficiency

55%

 

 

VAC @ 60HZ

120

 

 

WATTS / Low speed

70

DEFROST￿

 

DIMENSIONS 200ERVD

inches (mm)

FRESH AIR

ENTHALPIC

*All Duct Connections 6"(150mm)

FROM OUTSIDE

CORE

 

DAMPER

MOTOR

STALE AIR

 

 

 

 

 

 

TO OUTSIDE

 

 

 

PORT

 

 

 

 

 

 

FILTERS

 

 

BLOWERS

19"

(483)

 

 

 

 

 

 

 

 

 

 

 

 

*NOTE: Front clearance

 

 

 

FRESH AIR

 

 

of 25 inches (635 mm)

STALE AIR

 

 

 

 

is recommended

 

 

TO INSIDE

 

 

for servicing unit.

FROM HOUSE

 

 

 

 

 

 

 

 

 

 

 

31"

 

 

 

 

14 3/4"

CONDENSATE DRAINS

(787)

 

 

 

 

(375)

 

 

 

 

 

 

OPTIONS

99-104 Digital Electronic Timer - 20/40/60 min. (3 wire)

99-105Deluxe Programmable Control includes Programmable Time Clock, Dehumidistat and Air Sentry™

99-109 Air Sentry™ Air Quality Monitor designed to accept remotely mounted Control Pad.

99-186 Weatherhoods, Two - 6” (150mm) c/w 1/4” (6mm) mesh screen

DATE: __________________________

WARRANTY

Units carry a 5 year warranty on the energy recovery core and replacement parts.

All units conform to CSA and UL standards.

ERVs are not recommended for regions where the design temperature is below 25°F (-4°C)

 

511 McCormick Blvd.

PROJECT: __________________________________________

London, Ontario N5W 4C8

Ph: (519) 457-1904

 

Fx: (519) 457-1676

MECHANICAL CONTRACTOR: _____________________________

Email: nutech@lifebreath.com

Website: www.lifebreath.com

12

TI-200ERVD

0105

Image 12
Contents Contains 95MAX200ERVD Table of Contents ERV Questions & Answers Page Model 95MAX Engineering DataDimensions 155MAX inches mm Model 155MAXDimensions 200MAX inches mm Model 200MAXDimensions Maxtop inches mm Model Maxtop Dimensions 195DCS Model 195DCSModel 300DCS Thermally CONDUCTIVE, Patented Aluminum CoreDimensions 200ERV inches mm Model 200ERVDimensions 200ERVD Model 200ERVDFunction & Control To select mode of operation for ControlAir Optional Remote Controls NEW! AIR Sentry AIR Quality SensorUsing the Dehumidistat MAX Port Specifications Installation LocationInstalling AIR Ducts Supply AIR Ducting Dampers and GrillesInstallation Diagrams Simplified Installation Supply/Return Method Fully Dedicated System Pitot Tube AIR Flow Balancing Balancing Collar Instructions Inspect Exterior Hoods at least once a month Maintenance Routine for ERV for HRV, see previous Symptom Cause Solution OccupantTechnical Bulletin Residential Wiring Diagram McCormick Blvd. London, Ontario N5W 4C