E6581339⑥
3. Functional description
In this section, functions added by the installation of this expansion IO card option, on top of the standard inverter functions, are described.
*If the software version of inverter is less than V104, when OUT3 or OUT4 terminals is set as negative logic, it may output a flash pulse at inverter reset.
3.1Multi-function output terminal
Two output terminals and one relay output can be added. Function is similar to that of the output terminals of the inverter, so refer to the inverter instruction manual.
Parameter
Title | Function |
| Adjustment range | Default setting | |
f133 | Output terminal function selection 4 | (OUT3) | 0 - 255 | 254 | |
(Always OFF) | |||||
|
|
|
| ||
f134 | Output terminal function selection 5 | (OUT4) | 0 - 255 | 254 | |
(Always OFF) | |||||
|
|
|
| ||
f135 | Output terminal function selection 6 | (R1) | 0 - 255 | 254 | |
(Always OFF) | |||||
|
|
|
|
Monitor
Refer to the description on status monitor mode of inverter’s instruction manual.
The output terminal status can be monitored by the output terminal status parameter (fe07), and the parameter can be monitor by the serial communication.
fe07
bit No. |
| 15 | 14 | 13 | 12 | 11 | 10 | 9 | 8 |
| 7 | 6 | 5 | 4 | 3 | 2 | 1 | 0 | |||||||||||
Symbol |
|
|
|
|
|
|
|
|
| R2 |
|
| OUT |
| OUT |
| R1 | OUT | OUT | FL | OUT | OUT | |||||||
|
|
|
|
|
|
|
|
|
|
| 6 |
| 5 |
| 4 | 3 | 2 | 1 | |||||||||||
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
Note: The OUT5, OUT6 and R2 are the terminal function of the expansion IO card option 2.
10