Toshiba ETB003Z instruction manual Wiring, Input/output terminal interface

Page 9

E6581339⑥

2.2 Wiring

When conducting wiring, follow the instructions below.

Use shield wire for control signal line and ground the unit with shield wire (Use twisted pair shield cable for wiring of the analog monitor output.)

Never bind the signal line and main circuit connection wire together.

Fix the communication cables after connected.

Terminal Block

Applicable wire size

The wire length of

Using screwdriver

Tightening

peel off the end

(The blade tip)

torque

 

 

 

 

TB1

 

0.2 to 2.5 mm2

About 7mm

0.6mm thickness

0.5 to 0.6 Nm

 

and 3.5mm width.

 

 

 

 

 

 

TB2 and TB3

0.2 to 1.5mm2

About 5mm

0.4mm thickness

0.22 to 0.25 Nm

and 2.5mm width.

 

 

 

 

 

 

< Input/output terminal interface >

 

 

 

 

 

Terminal

 

Function

 

Electrical specification

 

 

Internal circuit

symbol

 

 

 

 

 

 

 

 

 

 

 

 

R1A

 

 

Configuration of 1C contact point

R1A

 

 

Relay contact

250Vac - 2A (cosφ=1)

 

R1B

 

 

R1B

 

 

 

point output

250Vac - 1A (cosφ=0.4)

 

 

 

Ry

R1C

 

 

 

 

 

30Vdc - 1A

 

R1C

 

 

 

 

 

 

 

 

 

 

 

No voltage contact input

 

SINK LogicSW=SINK(INT)

 

 

 

24Vdc - 5mA

 

P24/

 

SINK(PLC)

 

 

 

Sink input (common voltage 24V)

PLC

SW

 

 

 

 

 

SOURCE

 

 

 

ON

less than 10Vdc

 

 

SINK

 

 

 

 

 

 

 

 

 

 

 

(INT)

P24

 

 

 

OFF 16Vdc or more

 

 

 

 

 

 

 

LI1

 

 

 

 

 

Source input

 

LI2

 

2.2k ohm

 

 

 

ON

11Vdc or more

 

LI3

 

 

 

 

 

 

LI4

2.2k ohm

 

 

 

OFF

less than 5Vdc

 

 

 

 

 

 

CC

 

 

 

 

 

 

 

 

 

 

LI1

Contact point

Note:

 

 

SINK Logic (SW=SINK(PLC))

LI2

 

 

input Changeover

Even when an external power supply is

 

 

SINK(PLC)

LI3

P24/

 

of sink or source

used (in sink logic mode i.e. when

SW

 

LI4

PLC

SOURCE

 

 

SINK(PLC) is selected), connect

 

SINK

 

 

 

 

 

 

 

 

the reference potential-side (0V side)

 

(INT)

P24

 

 

 

LI1

 

 

 

 

cable from the power supply

 

 

 

 

 

 

 

LI2

 

2.2k ohm

 

 

 

to the CC terminal.

 

LI3

 

 

 

 

 

 

 

 

LI4

2.2k ohm

 

 

 

Lan current signal.

 

 

 

 

 

 

CC

 

 

 

 

 

Chose low current contacts to

 

 

 

 

 

 

 

avoid poor attaching.

 

SOURCE Logic (SW =SOURCE)

 

 

 

 

 

 

LI1

 

 

 

 

 

 

 

 

LI2

2.2k ohm

 

 

 

24Vdc power output (when SW1 is

LI3

 

 

 

 

 

 

 

 

LI4

 

2.2k ohm

 

 

 

in any position other than PLC)

 

 

 

 

24V power supply

 

 

SW

P24

 

24V internal output terminal

 

 

 

 

 

 

P24/

SINK

 

PLC/

 

 

24Vdc - 60mA max

 

SOURCE

 

 

 

(INT)

 

 

 

PLC

 

P24

Common terminal

If SW1 is turned to the PLC position,

CC

 

SINK(PLC)

 

this terminal can be used as a common

 

 

 

 

for external power

 

 

 

 

terminal when an external power

 

 

 

 

supply

supply is used.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

8

 

 

 

 

Image 9
Contents Expansion IO Card Option Safety precautions Safety precaution E6581339⑥ Confirmation on accessories IntroductionType of expansion IO option card Contents Name and function of each section AppearanceName of each section terminal Connection to the inverter Installing the IO card option in the VF-AS1/PS1Input/output terminal interface WiringTH1+ Tripping value about under 70 ohm Multi-function output terminal Functional descriptionParameter MonitorMulti-function input terminal 10V power supplyExternal thermal trip input TH1+, TH1 External diagram of option unit mm External diagramSpecification Environment SpecificationControl specification Warranty