Toshiba ETB003Z Installing the IO card option in the VF-AS1/PS1, Connection to the inverter

Page 8

E6581339⑥

2. Installing the IO card option in the VF-AS1/PS1

2.1 Connection to the inverter

Mandatory

(1) Turn off input power before installing.

Turn off the input power of VF-AS1/PS1 and wait for at least 15 minutes and then check that the CHARGE lamp on VF-AS1/PS1 is no longer lit.

(2)Securing the option to the inverter

a)Insert a flat-blade screwdriver in each of the two holes at the upper part of the front panel, release the panel mounting tab by pushing the screwdriver down, and remove the front panel cover.

b)Install the option in the inverter by fitting the tabs on the lower side of the option into the slots at the lower part of the inverter front panel.

c)Make sure the option is securely attached to the inverter. Then, check whether the plastic bosses on the inverter case have fitted in the holes at the upper and lower parts of the option*.

d)Insert the tabs at the lower part of the front cover into the slots at the lower part of the inverter to attach the front cover to the inverter.

a)

*When installing this option to below capacities, remove the Add-on type option case.

VFAS1: 200V 55, 75kW 400V 90 - 500kW

VFPS1: 200V 55 - 90kW

c)

400V 90 - 630kW

d)

b)

7

Image 8
Contents Expansion IO Card Option Safety precautions Safety precaution E6581339⑥ Type of expansion IO option card Confirmation on accessoriesIntroduction Contents Name of each section terminal Name and function of each sectionAppearance Installing the IO card option in the VF-AS1/PS1 Connection to the inverterWiring Input/output terminal interfaceTH1+ Tripping value about under 70 ohm Functional description Multi-function output terminalParameter Monitor10V power supply Multi-function input terminalExternal thermal trip input TH1+, TH1 External diagram External diagram of option unit mmControl specification SpecificationEnvironment Specification Warranty