NCM S7 Diagnostics
6.6.1Checklist for General CP Functions
Table
Problem | Possible Cause | Identifying the Cause and Remedy |
|
|
|
The Ethernet CP will not | Invalid configuration | Yellow STOP LED and red SF LED lit |
change to the RUN mode. | loaded on the Ethernet | continuously. |
| CP. | Call up the diagnostic buffer in NCM S7 |
|
| |
|
| Ethernet Diagnostics. |
|
| Example of an entry |
|
| CP STOP due to invalid CP parameter |
|
| assignment |
|
| What to do: |
|
| Correct the configuration of the Ethernet CP. |
|
|
|
| Switch set to STOP on the | Query the operating mode in NCM S7 |
| Ethernet CP. | Diagnostics. |
|
| Operating mode: STOP, Cause: switch set to |
|
| STOP |
|
| What to do: |
|
| Change the switch to RUN on the Ethernet CP |
|
|
|
SIMATIC NET NCM S7 for Industrial Ethernet | 189 |