Liebert Power Strips Configuration with Liebert MP Advanced Access Server, Make Connections

Page 4

CONFIGURATION WITH LIEBERT MP ADVANCED ACCESS SERVER

Liebert MP Advanced

Power Strip

(MP-C5120)

EIA-232 Port - Connect

to Power Strip EIA-232 Port

Liebert MP Advanced

Ethernet Port

Access Server

 

(MP-S5138)

 

Mounting Bracket on either side

POWER 1

3

5

8

EIA-232

EIA-232 Port

2

4

6

8

 

 

 

 

 

 

MP-DS74 Card With

Configurable

Communication Ports

EIA-232

 

 

 

 

 

 

ETHERNET

DS62 NETWORK INTERFACE

CX4 EIA-232 I/0

 

 

 

 

 

 

 

CX1CX2

DS74

 

 

 

 

 

 

 

 

 

CX3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ROUTE

LINE

 

 

4

3

2

1

 

 

100-240VAC

??????????

0.21-0.

MADE IN USA

On/Off Switch (not on all models)

MAKE CONNECTIONS

1.Connect power to the Liebert MP Advanced Access Server and turn the unit On (the On/Off switch is on the rear of the unit; some units do not have this switch; they are energized whenever their power cord is plugged into a power source).

2.Attach the adapter (RS-232 to RJ-45) to one end of a silver configuration cable (included) and connect that end of the cable to a COM port on a computer. Connect the other end of the cable to the EIA-232 port of the MP-DS62 card on your MP Advanced Access Server.

3.Plug one end of the second silver RJ-45 cable into any of the ports in the MP-DS74 module in your Liebert MP Advanced Access Server; plug the other end of the cable into the EIA-232 port on your MP Advanced Power Strip.

ESTABLISH COMMUNICATION WITH CARD

1.Use terminal emulation software, such as HyperTerminal™, to open a direct connection to the MP-DS62 card. Use the settings at right. Press Enter for the Main Menu, choose “C” and then “1” to configure the MP-DS62 port.

2.Enter “8” for Network Port Configuration (below left), then “7,” then “N” to disable DHCP (below right).

HYPERTERMINAL SETTINGS

Baud Rate: 9600

Data Bits: 8

Parity: None

Stop Bits: 1

Flow Control: N/A

 

 

Enter “N”

 

Enter “7”

to disable

Choose “8” to change

DHCP

Network Port

to change

 

DHCP setting

 

Configuration

 

 

 

4

Image 4
Contents Save These Important Safety Instructions QUICK-START Guide Opencomms EM or MP Advanced Access ServerConfiguration with Opencomms EM WHAT’S IncludedAssign AN IP Address Open the WEB Interface and LOGMake Connections Configuration with Liebert MP Advanced Access ServerEstablish Communication with Card SET the IP Address SET the Gateway AddressLiebert Corporation