Liebert Power Strips important safety instructions SET the IP Address, SET the Gateway Address

Page 5

SET THE IP ADDRESS

1.Select “1” to set the IP Address for Module 1. Enter an IP address (below). The address must be unique on your system (obtain this from your network administrator).

2.Press Enter to return to the Network Port Configuration menu.

Enter IP address

3. Choose “2” to set the Subnet Mask for your system (obtain this from your network administrator).

SET THE GATEWAY ADDRESS

1.Return to the Network Port Configuration menu and choose “3” to set the Gateway Address (the IP address of your network router). Follow the prompts to exit HyperTerminal and save your changes.

2.Verify that your settings are correct and were saved by using a command prompt to ping the MP-C/MP-S unit: Start>Run>CMD.

3.At the command prompt enter:

ping [IP address]

4. Press “Enter.”

5

Image 5
Contents QUICK-START Guide Opencomms EM or MP Advanced Access Server Save These Important Safety InstructionsWHAT’S Included Configuration with Opencomms EMOpen the WEB Interface and LOG Assign AN IP AddressEstablish Communication with Card Configuration with Liebert MP Advanced Access ServerMake Connections SET the Gateway Address SET the IP AddressLiebert Corporation