L404F,T,V PRESSURETROL® CONTROLLERS
SPECIFICATIONS
Model:
L404F,T,V PressureTrol® Controllers. See Table 1.
Table 1. Models with
|
|
| Subtractive Differentiala | Maximum Diaphragm | |||
| Operating Ranges |
| pressure | ||||
Model Number | kPa | psi | kPa | psi | kPa |
| psi |
L404F1060 | 15 to 100 | 2 to 15 | 15 to 40 | 2 to 6 | 170 |
| 25 |
L404F1078 | 35 to 350 | 5 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
|
|
|
|
|
|
|
|
L404F1094 | 140 to 2070 | 20 to 300 | 140 to 345 | 20 to 50 | 2410 |
| 350b |
L404F1102 | 70 to 1035 | 10 to 150 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
|
|
|
|
|
|
|
|
L404F1219c | 15 to 100 | 2 to 15 | 15 to 40 | 2 to 6 | 170 |
| 25 |
L404F1243c | 35 to 350 | 5 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
L404F1227c | 70 to 1035 | 10 to 150 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
L404F1235c | 140 to 2070 | 20 to 300 | 140 to 345 | 20 to 50 | 2410 |
| 350b |
L404F1300c | 415 to 1240 | 60 to 180 | 40 fixed | 6.0 Fixed | 1550 |
| 225 |
L404F1326 | 0 to 100 | 0 to 15 | 15 to 40 | 2 to 6 | 170 |
| 25 |
|
|
|
|
|
|
|
|
L404F1334 | 0 to 350 | 0 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
|
|
|
|
|
|
|
|
L404F1342 | 35 to 1000 | 5 to 145 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
|
|
|
|
|
|
|
|
L404F1359 | 70 to 2000 | 10 to 290 | 140 to 345 | 20 to 50 | 2410 |
| 350b |
L404F1367 | 7 to 55 | 1 to 8 | 5 to 14 | 0.75 to 2 | 170 |
| 25 |
|
|
|
|
|
|
|
|
L404F1375d | 35 to 350 | 5 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
L404F1383d | 70 to 1035 | 10 to 150 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
L404F1391d | 140 to 2070 | 20 to 300 | 140 to 345 | 20 to 50 | 2410 |
| 350b |
L404F1409d | 15 to 100 | 2 to 15 | 15 to 40 | 2 to 6 | 170 |
| 25 |
L404T1055 | 35 to 350 | 5 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
|
|
|
|
|
|
|
|
L404T1063 | 70 to 1035 | 10 to 150 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
|
|
|
|
|
|
|
|
L404V1087d | 70 to 1035 | 10 to 150 | 70 to 150 | 10 to 22 | 1550 |
| 225 |
L404V1095d | 35 to 350 | 5 to 50 | 40 to 100 | 6 to 14 | 590 |
| 85 |
aNominal at midscale operating range.
bBrass bellows instead of stainless steel diaphragm.
cModels with
d
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the TRADELINE® Catalog or price sheets for complete ordering number.
If you have additional questions, need further information, or would like to comment on our products or services, please write or phone:
1.Your local Honeywell Automation and Control Products Sales Office (check white pages of your phone directory).
2.Honeywell Customer Care 1885 Douglas Drive North
Minneapolis, Minnesota
In
International Sales and Service Offices in all principal cities of the world. Manufacturing in Australia, Canada, Finland, France, Germany, Japan, Mexico, Netherlands, Spain, Taiwan, United Kingdom, U.S.A.
2 |