Honeywell L404V, L404T Settings and Adjustments, Setpoint Adjustment, Scaleplate Adjustment

Page 6

L404F,T,V PRESSURETROL® CONTROLLERS

R

W

B

L404T

R

W

B (OMITTED)

L404V

B

R-W

B R-W

 

CONTROL

 

SET POINT

B-R BREAKS

 

 

(R-W MAKES)

DIFFERENTIAL

 

 

(ADJUSTABLE)

 

 

B-R MAKES

 

 

(R-W BREAKS)

B-R W

 

B-R W

 

 

SWITCH ACTION ON

 

SWITCH ACTION ON

PRESSURE RISE

 

PRESSURE FALL

BREAKS ON PRESSURE

MAKES ON PRESSURE

RISE TO SET POINT

RISE TO SET POINT

 

M1801B

Fig. 8. L404T,V terminal blocks and internal schematics.

OIL PRESSURE

MAIN OIL VALVE

CONTROLLER

SOLENOID

FLAME

 

SAFEGUARD

 

CONTROL

 

L2

 

 

M9789

Fig. 9. Hookup of an oil pressure controller used on a

single burner system with an integral oil pump.

 

OTHER

 

CONTROLLERS,

OIL PRESSURE

LIMITS, AND

INDICATES CLOSED SWITCH CONTACTS.

M19639B

 

Fig. 11. Operation of switch on pressure rise and fall.

Setpoint Adjustment

Turn the pressure adjusting screw on the top of the controller (Fig. 12) to adjust the setpoint. Turn the differential adjusting screw to the desired pressure difference between switch opening and switch closing.

NOTE: When the main scale setting is at the lower end of the operating range, the differential range will be less than the differential setting by approximately 20 percent.

DIFFERENTIAL

PRESSURE ADJUSTING SCREW

ADJUSTING SCREW

CONTROLLER

INTERLOCKS

L1

FLAME

SAFEGUARD

(HOT)

CONTROL

 

L2

L2

 

M9790

SCALEPLATES

MAIN SCALE PRESSURE INDICATOR

GROUND SCREW

Fig. 10. Hookup of an oil pressure controller used on a single burner or multiburner system with an external oil pump.

SETTINGS AND ADJUSTMENTS

When the pressure at the control rises above the L404 setpoint, a circuit opens between the R-B terminals. During a pressure fall, R-B will close at the setpoint pressure minus the switch differential.

For example, if a controller is set to differential B (see Fig.11) with a controller setpoint of A, R-B will open when the pressure rises to A. Then during a pressure fall, the R-B terminals will close when the pressure drops to C (A minus differential B).

For make on rise applications, the switch is wired to R-W terminals. The R-W circuit will close on pressure rise to the setpoint. R-W will open again on a pressure drop past the switch differential.

DIFFERENTIAL

SETTING

INDICATOR

DIAPHRAGM

OPERATING

ASSEMBLY

LEVER

 

M19640A

Fig. 12. view of L404 PressureTrol® Controller.

Scaleplate Adjustment

The L404F,T,V has been carefully calibrated during manufacture and should not require recalibration.

However, if recalibration is necessary, remove the cover and loosen the setscrews which hold the scaleplate. Adjust the plate up or down, as required, to bring the device into calibration. Tighten the setscrews securely and replace the cover.

71-2429—2

6

Image 6
Contents Features Application ContentsModel SpecificationsOrdering Information Model Number KPa PsiSwitch Ratings Amperes Switch State 120 Vac 240 Vac InstallationWhen Installing This Product… Dimensions See FigLocation and Mounting L404F Location and Mounting L404T,VWiring Using with Preheated OilSettings and Adjustments Setpoint AdjustmentScaleplate Adjustment Checkout Automation and Control Solutions