L404F,T,V PRESSURETROL® CONTROLLERS

CHECKOUT

After the controller has been installed, wired and adjusted, it should be tested with the system in operation. First, allow the system to stabilize. Then, observe the operation of the controller while raising and lowering its setpoint. Pressure should increase when the setpoint is raised and decrease when the setpoint is lowered.

Also, check the make and break points of the controller. If they do not agree with a separate, accurately calibrated pressure gauge, a slight adjustment of the scaleplate(s) may be necessary.

Use accurate pressure testing equipment when checking out the controller. Do not rely on inexpensive gauges. The controllers are carefully calibrated at the factory.

7

71-2429—2

Image 7
Contents Contents Features ApplicationModel Number KPa Psi SpecificationsOrdering Information ModelDimensions See Fig InstallationWhen Installing This Product… Switch Ratings Amperes Switch State 120 Vac 240 VacLocation and Mounting L404T,V Location and Mounting L404FUsing with Preheated Oil WiringSetpoint Adjustment Settings and AdjustmentsScaleplate Adjustment Checkout Automation and Control Solutions