L404F,T,V PRESSURETROL® CONTROLLERS
IMPORTANT
When making pipe connections, use pipe dope sparingly to seal the joints; any excess dope may clog the small hole in the fitting and prevent the controller from operating properly.
Location and Mounting (L404F)
Locate the L404F where the ambient temperature will not exceed 66°C (150°F). The L404F can be mounted near the pressure gauge, at a remote location, in a fitting provided by the boiler manufacturer, or in a special mounting on low water cutoffs. The L404F should always be mounted above the water line in steam boiler applications.
NOTE: For accurate operation, supplemental heat should be added to installations where temperatures fall below
A steam trap must be connected between the L404F and the boiler (see Fig. 2) to prevent boiler scale and corrosive vapors from attacking the elbows or diaphragm.
Remote Mounting
Excessive vibration at the boiler may affect the operation of the L404F. In these cases, the L404F should be remotely located, subject to the following:
1.All piping must be suitable and properly pitched to drain all condensation back to the boiler.
2.The remote mounting must be solid.
3.A steam trap must be used at one end of the piping.
Boiler Mounting
If it is not convenient to mount the L404F adjacent to the pressure gauge, install a steam trap at the location recommended by the boiler manufacturer, then screw the device directly to the steam trap.
Location and Mounting (L404T,V)
Location
PRESSURE
PRESSURE GAUGE
CONTROLLER
TEE |
|
| 14026 | 1 |
|
|
| |
| STEAM TRAP | ||
| (SIPHON LOOP) | ||
|
| ||
(114.3 TO 139.7) |
|
|
|
|
|
|
|
NOTE: For most accurate operation, supplemental heat should be added to installations where the temperature falls below
BOILER
11/4 IN. BLACK IRON PIPE WITH 1/4 - 18 NPT EXTERNAL THREADS ON BOTH ENDS AND
M8934B
Fig. 2. Steam trap mounting.
Mounting
Mount the oil pressure controller directly on the main pipe. Insert a tee in the pipe line, and connect a pipe nipple of appropriate size to the tee (see Fig. 4). Screw the hexagonal fitting
Pressure Gauge Mounting
To mount beside a pressure gauge, remove the gauge, and install in its place the steam trap with a tee on top. Mount the PressureTrol® unit and pressure gauge on the side of the tee by means of nipples and elbows (see Fig. 2).
Make all pipe connections in accordance with approved standards. Use only a small amount of pipe compound to seal the connection joints. Excess pipe compound may clog the orifice in the pipe fitting and prevent the controller from operating properly.
MAIN | STRAINER |
|
|
|
|
|
|
OIL |
|
|
|
| ATOMIZER | ||
|
|
|
|
| |||
LINE |
|
|
|
|
| ||
|
|
|
|
|
|
| |
MANUAL |
|
|
|
|
|
|
|
SHUTOFF | OIL | LOW OIL | LOW OIL |
| HIGH OIL | MANUAL | TO OIL |
VALVE | PUMP WITH | PRESSURE | TEMPERATURE | RECIRCULATING | PRESSURE | BURNER | |
| PRESSURE RELIEF | CONTROLLER |
| VALVE AND SAFETY | CONTROLLER | SHUTOFF |
|
|
|
|
| SHUTOFF VALVE |
| VALVE |
|
|
|
|
|
|
|
| |
|
|
|
|
| ATOMIZING MEDIUM |
| |
|
|
|
|
| (AIR OR STEAM) | M17861 |
Fig. 3. Typical locations of pressure controllers in an oil burner system.
4 |