Iomega EP510 Directions, Electrical Connections, Terminal Block Transducer Models, Calibration

Page 5

M-4109/1104 IP510, EP510, IP511, EP511 SERIES A

ELECTRICAL CONNECTIONS

PRECAUTIONS TO BE OBSERVED DURING INSTALLATION

These Transducers were tested at the EMC Test Centre, Dunfermline, Fife, KY11 5LB to the Electromagnetic Compatibility Directive effective January 1, 1996. The relevant EMC specifications tested were the following: EN 50081-1 (1992) and EN 50082-2 (1992). A Technical Construction File, Serial #107 was written and Certificate of Conformity issued by a Competent Body.

EN 50081-1 (1992): Test results confirmed that no precautions need to be observed during installation regarding electro- magnetic emissions from the 510 or 511 Series Transducers.

EN 50082-2 (1992): The following precautions should be taken during installation to maintain the advertised accuracy speci- fications. The input wiring to the transducer should be isolated from other high voltage transient wiring. The momentary switching on and off of nearby relays, motors, or other high capacitive or inductive loads can have a minor effect on the accuracy specification (0.25% of Span). Any change in output pressure is minimal and momentarily, and is considered to be within the performance capabilities. Use of a ferrite bead collar on the input wires entering the transducer is recommended should installation next to high electromagnetic interference be necessary.

WARNING: In explosive atmospheres, electrical power must be removed from the transducer before attempting to remove the cover and until the cover is fully reinstalled. Failure to do so may result in electrical spark or explosion. CAUTION: Care must be used when inserting wires into the NPT port. Wires must not enter below the circuit board due to sensitive mechanical components.

DIRECTIONS

1.Remove the cover (see WARNING above).

2.Bring wiring to the terminal block, located on the circuit board, through 1/2 NPT electrical conduit connection. 18 A.W.G. is recommended; 14 A.W.G. is the maximum wire size. Connect wires to the terminal block per TABLE 2. Care must be exercised to prevent damage to delicate internal parts when inserting wiring through the 1/2” NPT conduit opening.

3.An internal grounding screw is provided on all units to facilitate separate ground when required. An external grounding lug is also provided on NEMA 4X enclosures.

4.Reinstall the cover tightly using all o-rings and locking devices to insure compliance with Agency Approvals.

TABLE 2: ELECTRICAL CONNECTIONS

TERMINAL BLOCK

I / P TRANSDUCER MODELS

E / P TRANSDUCER MODELS

 

 

 

POSITION # 1

( -- ) NEGATIVE SIGNAL

( + ) POSITIVE SIGNAL

 

 

 

POSITION # 2

NOT USED

COMMON GND FOR SIGNAL

AND SUPPLY

 

 

POSITION # 3

( + ) POSITIVE SIGNAL

( + ) POSITIVE SUPPLY

 

 

 

CALIBRATION

5

Image 5
Contents EP510, IP510, EP511, IP511 Series Servicing North America AIR Connections Supply ContentsOutput GaugeDirect Mounting Mounting GeneralElectrical Connections DirectionsTerminal Block Transducer Models CalibrationPneumatic Maintenance MaintenanceElectrical Maintenance Enclosures Entity ParametersNonincendive Nema 4X, Replacement Parts for Cover Locking Device Nema 4X, Replacement Cover O-RINGSExplosion & DUST-IGNITION Proof Certifications Part Name Part NumberKIT Name Kits511 Series I/P and E/P Transducer Specifications WARRANTY/DISCLAIMER Temperature