M-4109/1104 IP510, EP510, IP511, EP511 SERIES A

AIR CONNECTIONS

SUPPLY

Connect air supply to 1/4 NPT port marked "IN." If the above specifications are not met, possibility of internal clogging exists. Also see MAINTENANCE section.

OUTPUT

Connect output to 1/4 NPT port marked "OUT."

GAUGE

The plugged 1/8 NPT port in the base of the transducer is internally connected with the "OUT" port. A pressure gauge can be attached to this port to monitor output pressure.

 

CONTENTS

 

 

Air Connections

. . . .Page 1

 

Pressure Requirements

. . . .Page 2

 

Mounting

. . . .Page 2

 

Direct Mounting

 

 

Mounting Kits

 

 

Electrical Connections

. . . .Page 3

 

Precautions to be observed during installation

 

 

Calibration

. . . .Page 4

 

Maintenance

. . . .Page 5

 

Agency Approvals, Special Notes, and Cautions

.Page 5 & 6

 

Kits

. . . .Page 7

 

Specifications

. . . .Page 8

 

 

 

WARNING

 

In order to get optimal service from this transducer and ensure warranty coverage the following MUST be followed:

The supply air quality to this instrument must be instrument quality air as defined by ISA Standard 57.0.01-1996.

1.Dew point not higher than 35˚F.

2.No particulates larger than 3 microns in size.

3.Maximum oil content of 1 ppm.

No mechanical adjustments or calibrations are necessary or allowed. All calibration MUST be done with electrical poten- tiometers on the enclosed circuit board only. See “CALIBRATION” section of instructions for more information.

TABLE 1: SUPPLY PRESSURE REQUIREMENTS

Standard Output

0-2

0-5

0-30

0-60

0-100

0-120

1-17

3-9

3-15

3-27

6-30

Calibration

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

 

 

 

 

 

 

 

 

 

 

 

 

Transducer

20-45

20-45

50-90

80-120

110-130

130-140

30-70

20-100

20-100

35-100

35-100

Supply Pressure

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

PSI

 

 

 

 

 

 

 

 

 

 

 

 

3

Image 3
Contents EP510, IP510, EP511, IP511 Series Servicing North America Gauge ContentsAIR Connections Supply OutputDirect Mounting Mounting GeneralCalibration DirectionsElectrical Connections Terminal Block Transducer ModelsMaintenance Electrical MaintenancePneumatic Maintenance Entity Parameters NonincendiveEnclosures Part Name Part Number Nema 4X, Replacement Cover O-RINGSNema 4X, Replacement Parts for Cover Locking Device Explosion & DUST-IGNITION Proof CertificationsKIT Name Kits511 Series I/P and E/P Transducer Specifications WARRANTY/DISCLAIMER Temperature