Pelco VMX300 installation manual CM9760-REL Relay Interface Unit, RDA RDB RS-422 Reversed Cable

Page 43

CM9760-REL RELAY INTERFACE UNIT

To connect a CM9760-REL relay interface unit to the VMX300(-E), complete the following steps (refer to the CM9760-REL Installation/Operation manual for detailed instructions):

1.Connect the relay unit to the VMX300(-E) as described below for the appropriate communication mode:

Direct serial: Connect an RS-232 to RS-422 adapter to COM 1 or COM 2 on the VMX300(-E) workstation, and then wire the adapter to a wall block (user-supplied), as shown in Figure 37. Using an RS-422 reversed data cable, connect the wall block to the IN port on the CM9760-REL.

VMX300(-E)

RS-232

45

36

WALL BLOCK

RS-232 TO RS-422

ADAPTER

TD(A) TD(B) RD(A) RD(B) GND +12 VDC

2

7

TD(A)

8

1

TD(B)

 

RD(A)

RD(B)

RS-422 REVERSED CABLE

CM9760-REL

Figure 37. CM9760-REL Direct Serial Connection

Internet Protocol: Connect the RS-422 IN port on the relay unit to an RS-422 serial port on a networked device, such as a PelcoNet encoder. If the networked device does not have an RS-422 serial port, use an RS-232 to RS-422 adapter. (Refer to Figure 26 on page 28 for a sample illustration.)

2.(Optional daisy-chaining): If you are connecting multiple relay units in a daisy-chain series, use the data cables provided with the relay units to connect the first unit’s RJ-45 OUT port to the next unit’s RJ-45 IN port.

3.After installing system hardware, complete the following configuration steps:

a.Add the REL driver and the relay interface unit to the VMX300(-E) server configuration. Each unit in a daisy-chain configuration must be added to the VMX300(-E), and then configured with the appropriate settings. Note that the recommended baud rate for communication between VMX300(-E) and the CM9760-REL is 19200. You must set this baud rate on the Communications tab when you configure the CM9760-REL device in the VMX300(-E). (Refer to the VMX300(-E) Server Configuration Manual for instructions.)

b.Change the CM9760-REL settings to the following recommended settings for VMX300(-E) communication: RS-422, 19200 baud, no parity, 8 data bits, 1 stop bit. (Refer to the CM9760-REL Installation/Operation manual for instructions.)

C1552M-C (7/07)

39

Image 43
Contents Rear View AddendumVMX300-E Monitor Outputs How to Connect a Single Monitor to a VMX300-E WorkstationModel Workstations VMX300-E Analog Video InputsISO9001 Installation Manual Page Contents List of Tables List of IllustrationsImportant Safety Instructions Video Quality Caution Regulatory NoticesDescription VMX300 Models ModelsVMX300-E-CL-0 Client VMX300-E ModelsCompatible Products VMX300E-B Backup ServerDocumentation Resources Typical Applications Matrix SwitchersPelco Ascii Switchers Coaxitron and Fixed Camera Transmission Looping Camera Outputs DX8000 and DX9000 Series DvrsConnecting a DVR Method Network Pelconet Transmission SystemsNetworkip Example 3 of a PelcoNet Configuration Sample VMX300-E System with the NVR300 NVR300 Network Video RecorderParts List InstallationUSER-SUPPLIED Parts Mounting Rack Mount InstallationFront View Rear View VMX300-E Connections to the Network VMX300-E ConnectionsVMX300-E Keyboard and Mouse Right VGA Monitor Video Input Direct Serial Connection External DevicesInternet Protocol KBD300A Direct Serial Connection KBD300A KeyboardNetwork Keyboard Communications tab, Connection Type Select Direct Serial SPECTRA/ESPRIT Control ConnectionsConnect Ground on ONE END only CM6700 SwitcherCM6800 Port Programming CM6800 SwitcherAlternate CM6800 Connection CM9700 Matrix Switching Systems Alternate CM9700 Connection CM9760-ALM Alarm Interface Unit RDA RDB RS-422 Reversed Cable CM9760-REL Relay Interface UnitIP-BASED Devices Serial Output DevicePower Cables Appendix Changing the Port Settings of a VMX300-E COM PortELECTRICAL/ Video SpecificationsPage Product Warranty and Return Information ISO9001