Pelco BB5L operation manual Wire Gauge

Page 11

EXAMPLE: A dome that requires 90 vA and is installed 31 feet (9 m) from the transformer would require a minimum wire gauge of 20 AWG.

NOTE: Distances are calculated in feet; values in parentheses are meters.

Table B. 24 VAC Wiring Distances

The following are the recommended maximum distances for 24 VAC with a 10- percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for AC-powered devices.)

Wire Gauge

 

 

20

18

16

14

12

10

 

 

 

 

 

 

 

 

 

 

 

10

283

451

716

1142

1811

2880

 

 

 

(86)

(137)

(218)

(348)

(551)

(877)

 

 

 

 

 

 

 

 

 

 

 

20

141

225

358

571

905

1440

 

 

 

(42)

(68)

(109)

(174)

(275)

(438)

 

 

 

 

 

 

 

 

 

 

 

25

113

180

286

457

724

1152

 

 

 

(34)

(55)

(87)

(139)

(220)

(351)

 

 

 

 

 

 

 

 

 

 

 

30

94

150

238

380

603

960

 

 

 

(28)

(45)

(72)

(115)

(183)

(292)

 

 

 

 

 

 

 

 

 

 

 

40

70

112

179

285

452

720

 

 

 

(21)

(34)

(54)

(86)

(137)

(219)

 

 

 

 

 

 

 

 

 

 

 

50

56

90

143

228

362

576

 

 

 

(17)

(27)

(43)

(69)

(110)

(175)

 

 

 

 

 

 

 

 

 

loadto

 

60

47

75

119

190

301

480

 

 

(14)

(22)

(36)

(57)

(91)

(146)

 

 

 

 

 

 

 

 

 

 

 

70

40

64

102

163

258

411

 

 

 

(12)

(19)

(31)

(49)

(78)

(125)

fromdistancetransformer

consumedvATotal

 

 

 

 

 

 

 

120

23

37

59

95

150

240

 

80

35

56

89

142

226

360

 

 

 

(10)

(17)

(27)

(43)

(68)

(109)

 

 

90

31

50

79

126

201

320

 

 

 

(9)

(15)

(24)

(38)

(61)

(97)

 

 

100

28

45

71

114

181

288

 

 

 

(8)

(13)

(21)

(34)

(55)

(87)

 

 

 

 

 

 

 

 

 

 

 

110

25

41

65

103

164

261

 

 

 

(7)

(12)

(19)

(31)

(49)

(79)

 

 

 

 

 

 

 

 

 

 

 

 

(7)

(11)

(17)

(28)

(45)

(73)

Maximum

 

 

 

 

 

 

 

 

 

140

20

32

51

81

129

205

 

130

21

34

55

87

139

221

 

 

 

(6)

(10)

(16)

(26)

(42)

(67)

 

 

 

(6)

(9)

(15)

(24)

(39)

(62)

 

 

 

 

 

 

 

 

 

 

 

150

18

30

47

76

120

192

 

 

 

(5)

(9)

(14)

(23)

(36)

(58)

 

 

 

 

 

 

 

 

 

 

 

160

17

28

44

71

113

180

 

 

 

(5)

(8)

(13)

(21)

(34)

(54)

 

 

 

 

 

 

 

 

 

 

 

170

16

26

42

67

106

169

 

 

 

(4)

(7)

(12)

(20)

(32)

(51)

 

 

 

 

 

 

 

 

 

 

 

180

15

25

39

63

100

160

 

 

 

(4)

(7)

(11)

(19)

(30)

(48)

 

 

 

 

 

 

 

 

 

 

 

190

14

23

37

60

95

151

 

 

 

(4)

(7)

(11)

(18)

(28)

(46)

 

 

 

 

 

 

 

 

 

 

 

200

14

22

35

57

90

144

 

 

 

(4)

(6)

(10)

(17)

(27)

(43)

 

 

 

 

 

 

 

 

 

 

Pelco Manual C1488M-A (9/98)

11

Image 11
Contents Listed Contents General Important Safeguards and WarningsRegulatory Notices Pendant Models Unpacking InstructionsRecommended Tools IN-CEILING ModelsFCC DescriptionModels CertificationsCeiling and Back BOX Preparation Installation for IN-CEILING ModelsProceed to .2, Wiring RG6/U WiringProceed to .3, Back BOX Installation Maximum DistanceHard Ceiling Ceiling Tile Wiring Diagram for Spectra Ver .0 and Spectra Wire Gauge Proceed to .4, Back BOX Connections Back BOX InstallationBack BOX Connections Dome 1 Power Dome 2 Power Dome 3 PowerRX+ TX+ From controller To 4-Wire terminal on circuit boardSURFACE-MOUNT Installation Installation for Pendant ModelsPENDANT-MOUNT Installation Symptom LED does not light TroubleshootingGeneral SpecificationsMechanical ElectricalSD5 Series Dimension Drawing Pelco Manual C1488M-A 9/98 Returns Warranty and Return InformationWarranty