Electrical
Electrical Specification
Model | HIP | HIP | HIP | HIP |
| HIP | HIP |
| - 205BE11, | - 200BE11, | - 195BE11, | - 190BE11, |
| - 186BE11, | - 180BE11, |
| - 205BE11- BO2 | - 200BE11- BO2 | - 195BE11- BO2 | - 190BE11- BO2 | - 186BE11- BO2 | - 180BE11- BO3 | |
Cell Number in Series [Pieces] | 96 | 96 | 96 | 96 |
| 96 | 96 |
Maximum Power (Pmax) [W] | 205 | 200 | 195 | 190 |
| 186 | 180 |
Maximum Power Voltage (Vmp) [V] | 56.7 | 55.8 | 55.3 | 54.8 |
| 54.4 | 54.0 |
Maximum Power Current (Imp) [A] | 3.62 | 3.59 | 3.53 | 3.47 |
| 3.42 | 3.33 |
Open Circuit Voltage (Voc) [V] | 68.8 | 68.7 | 68.1 | 67.5 |
| 67.0 | 66.4 |
Short Circuit Current (Isc) [A] | 3.84 | 3.83 | 3.79 | 3.75 |
| 3.71 | 3.65 |
Cell Type |
|
| HIT* (hybrid of a- Si and mono c- Si) |
|
| ||
Maximum System Voltage [V] | 1000 | 1000 | 1000 | 1000 |
| 1000 | 1000 |
Factory Installed Bypass Diode | Yes | Yes | Yes | Yes |
| Yes | Yes |
Weight [kg] | 14 | 14 | 14 | 14 |
| 14 | 14 |
*HIT= Hetero junction with Intrinsic
Module wiring
>The maximum number of HIP- xxxNHE5,
>The maximum number of HIP- BE11,
>When your PV system includes other components (batteries, charge controllers, inverters, etc.), be sure to follow the safety recommendations of their manufactures.
>These modules contain factory installed bypass diodes. If these modules are incorrectly connected to each other, the bypass diodes or cable or junction box may be damaged.
Array Wiring
The term “array” is used to describe the assembly of several modules on a support structure with associated wiring.
Use copper wire that is sunlight resistant and is insulated to withstand the maximum possible system open circuit voltage. Check your local codes for requirements.
Electrical Protection
The HIP- xxxNHE5,
If necessary, the module or array can be grounded.
Module Terminations
A junction box as terminal enclosure is equipped for electrical connections on SANYO modules.
The HIP- xxxNHE5,
Use these MC plugs for electrical connections. Please contact your local dealer with questions regarding other electrical connections for modules.
Junction box configuration and description of terminals (for reference)
Modules equipped with one junction box contain terminals for both positive and negative polarity, and bypass diodes.
Two terminals are dedicated to each polarity (with the polarity symbols engraved onto the body of the junction box ) (see Fig3).
Cable |
|
Connector |
|
(MC Plug) |
|
negative ( - ) | positive ( + ) |
Figure3: Configuration of
junction box
4 | Printed in Europe 20.10.2006 |