Figure 3
*Grounded cold water pipe must have metal continuity to electrical ground and not be interrupted by plastic, rubber or other electrical lnsulatin connectors such as hoses, 8i ngs. washer or gaskets
(includi water meter or pump). Any elec7% cat Insulating connector should be Jumped as shown in Figure 3 with a length of
Direct wiring connection_
1. Strip the outer covering back 3 Inches from the end exposing the three wires.
2.Strip the Insulation back 1 inch from the end of each wire. Form the bare wires into a
I Direct wiring connection
Figure 4
3.Loosen, do not remove, the center,
4.Slide the end of the neutral (white or center) wire under the screw head with the open side of the screw hook on the right. Squeeze the wire together to form a loop.
5.lighten the screw firmly.
6.Connect the remalnlng 2 wires to the outer screws the same way.
7.Tighten strain relief screws firmly.
A.
If local codes permlt c01 lnection of
,,1exte ,nal grounding
Figure 5
\1. Disconnect the power supply.
2.Remove the terminal I>lock covers by removing the screw s ?own in Figure 5.
Rear panel 3/4’.
strain relief (outside di yer)
Figure 6
3.Attach a 3/4’,
gw;(;)eundlw
(green wlth yellow stripes)
|
|
|
| center, |
to fused |
|
| silver- | |
disconnect | box | colored | ||
or approved |
|
| termlnal | |
wiring | device |
| tor | block |
power | supply | cord | screw |
| copper | - |
power | supply | cord |
with | strain | relief |
(30 | amperes) | |
Grounded | Neutral | |
Figure | 7 |
4.Connect the neutral wire of each power supply cord to the center,
silvercolored termlnal of the terminal block;. Connect the other wires to the outer termlnals. (See Flgure 7.)
Tighten screws.
5.Replace the termlnal block covers by first installlng the tab of each cover Into tie slot of the dryer rear panel. (See Figure 5.) Secure the covers with the mounting screws.
6.Tighten the strain relief clamps on the power supply cords. (See Figure 6.)
Page 4