Exhaust reqdrements
Exhaust materials are not supplied.
Fire Hazard
l Do Not use
l Do Not use metal duct smaller than four Inches in diameter.
l Do Not use exhaust hoods with magnetic latches. Improper air supply for exhaustlng may result in a fire.
l Check that exhaust system is not longer ttian specified. Exhaust systems longer than specified will:
- Accumulate Ilnt.
-Shorten the life of the product.
-Reduce performance, resulting In longer drying times and Increased energy
usage.
Failure to follow
l Dryers must be exhausted to
Metal flexible duct mus be fully extended and supports d when the dryers are In final pc
completely | opeti | to allc IW |
adequate | exhaust | air tc Bflow. |
Allow as much room as possible when using elbows or rr aking turns. Bend duct gradually to avold kinklng. Remove 8x1~s:; flexible duct to bvold sagging and ki nklng that may cause reduced alr low.
The exhaust duck can t = routed up. down, left, right or strais ht out the back of the dryers. The lower dryer can also be exhausted hrough the bottom of the dryer. PrcIduct dimensions and recesse 3 area requirements are glven Dn Page 9.
For exhaust systems not covered by the exhaust length cl )art. see WhIrlwool Service Manuc & ‘Exhausting WhIrlpool Dryers’, Part No. 603197, available fit m your Whlrlpool parts diitributc r.
Side or Bottom Exhaust: The maxlmum length of the exhaust system If dryer is exhausted out the side or bottom is 16 feet with two external elbows and hood.
Service check: The back pressure In any exhaust system used must not exceed 0.6 Inches of water column measured with an inclined manometer at the point that the exhaust system connects to the dryers.
If the dryers are installed in a confined area, they must be exhausted to the outside and provislon must be made for enough air for combustion and ventilation. Check governlng codes and ordinances. Also refer. to the ‘Recessed area and closet installation instructions.’ Page 9.
An exhaust hood should cap the exhaust duct to prevent exhausted air from returnlng into the dryers.
The outlet hood must be at least 12 inches from the ground or any object that may be In the path of the exhaust.
the outside.
l Do Not exhaust dryers into chimney, furnace cold air duct, attlc or crawl space, or any other duct used for venting.
l Clean the exhaust system frequently.
l Do Not Install flexible duct under wall, ceiling or floor materials.
Accumulated lint could result in fire or cause moisture damage.
Use duct tape to seal all joints.
|
|
|
|
|
|
|
|
|
|
| A main exhaust duct can be used | ||||||||||
Rear | Exhaust: | The maxim | urn | length | for | exhausting | a | group | of dryers. | ||||||||||||
Main | exhaust | duct | should | be sized | |||||||||||||||||
of | the exhaust | system | dc !pends | on | to | remove | 200 CFM | of | alr | per |
| ||||||||||
the | type | of | duct, | the | nul | nber | of | dryer. |
|
| lint | screens | |||||||||
elbows, | and |
| the | type | of | exhaust |
| of | proper | design | may |
| be | used | In | ||||||
hood. | The | maximum | ler | gth | for | both | the | main | exhaust | duct |
| if checked | |||||||||
rigld | and | flexlble | duct | is :hewn | in | and | cleaned | frequently. |
| The | room | ||||||||||
the | chart. |
|
|
|
|
|
|
|
| where | the | dryers | are | located | . | ||||||
|
|
|
|
|
|
|
|
|
|
| should have |
| air | equal | to |
or greater than the CFM of all the
Aps@%!dryers in the room.
good | better |
exhaust airflow | exhaust oifflow |
Page 6
A’A’
Exhaust Hood T rpe
lumber of 0” turns
A
43 | Ft. | Maxlmum | |||
length | of 4 | ||||
33 | Ft. | dia. | rigid | ||
23 | Ft. | ||||
metal |
| duel | |||
|
|
| |||
30 | Ft. | Maximum | |||
length | of 4 | ||||
24 | Ft. | ||||
dia. | flexibl | ||||
16 Ft. | |||||
metal |
| due | |||
|
|
|
air flow 1main collector dud