E. EXHAUST REQUIREMENTS

1.General Exhaust Duct Work Information

Exhaust duct work should be designed and installed by a qualified professional. Improperly sized duct work will create excessive back pressure which results in slow drying, increased use of energy, overheating of the dryer, and shutdown of the burner by the airflow (sail) switches, burner hi-limits, or basket (tumbler) hi-heat thermostats.

CAUTION: DRYER MUST BE EXHAUSTED TO THE OUTDOORS.

CAUTION: IMPROPERLY SIZED OR INSTALLED EXHAUST DUCT WORK CAN CREATE A POTENTIAL FIRE HAZARD.

The duct work should be laid out in such a way that the duct work travels as directly as possible to the out- doors with as few turns as possible. Single or independent dryer venting is recommended.

Horizontal Venting:

When single drying venting is used the length of duct work from the dryer to the outside exhaust outlet should not exceed fifteen (15) feet. The minimum diameter of this duct work must be at least 10-inches. In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust outlet should not exceed (15) feet. The shape of the duct work is not critical so long as the minimum cross- sectional area is provided. It is suggested that the use of 90° turns be avoided; use 30° and/or 45° angles instead. The radius of the elbows should preferably be 1-1/2 times the diameter of the duct. Including basket (tumbler)/dryer elbow connections or elbows used for outside protection from the weather, no more than two (2) elbows should be used in the exhaust duct run. If more than two (2) elbows are used, the cross sectional area of the duct work must be increased. ALL duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Inspection door should be installed at strategic points in the exhaust duct work for periodic inspection and clean-out of lint from the duct work.

Vertical Venting:

When single dryer venting is used the length of the duct work from the dryer to the outside exhaust outlet should not exceed twenty (20) feet. The minimum diameter of this duct work must be at least 12- inches. In the case of multiple (common) dryer venting, the distance from the last dryer to the outside exhaust outlet should not exceed twenty (20) feet. The shape of the duct work is not so critical so long as the minimum cross sectional area is provided. It is suggested that the use of 90º turns be avoided; use 30º and/or 45º bends instead. The radius of the elbows should preferably be 1-1/2 times the diameter of the duct. ALL duct work should be smooth inside with no projections from sheet metal screws or other obstructions which will collect lint. When adding ducts, the duct to be added should overlap the duct to which it is to be connected. ALL duct work joints must be taped to prevent moisture and lint from escaping into the building. Inspection door should be installed at strategic points in the exhaust duct work for periodic inspection and clean-out of lint from the duct work.

IMPORTANT: Exhaust back pressure measured by a manometer in the exhaust duct should not exceed 0.3 inches of water column.

15

Image 19
Contents ML-78 Retain This Manual In a Safe Place For Future Reference For Your Safety Page Table of Contents Section Procedure for Functional Check of Replacement Important Information SectionWhat to do if YOU Smell GAS Safety PrecautionsStandards Specifications SPECIFICATIONS/COMPONENT IdentificationSpecifications Component Identification Dryer Rear View Location Requirements Installation ProceduresUNPACKING/SETTING UP Dryer Enclosure Requirements Fresh AIR Supply Page Exhaust Requirements Not be Reduced Anywhere Down Stream of the Dryer Reduced Anywhere Down Stream of the Dryer Page Electrical Information MLG-78 Gas MLS-78 Steam Page Black Positive White Neutral Green Ground Page Electrically Heated Models only Page GAS Information Type of Gas Page Page Operating Steam Pressure Steam InformationSteam Damper System Compressed Air Supply Air Pressure Page Page Preparation for OPERATION/START-UP Preoperational Tests Page Preoperational Instructions Shut Down Instructions Service SERVICE/PARTS InformationParts Returning Warranty Cards Warranty InformationReturning Warranty Parts Page Cleaning Routine MaintenanceSteam Dryers Timing Legend Reversing Timer SPIN/DWELL AdjustmentsData Label Data Label LOCATION/INFORMATIONSerial Number Section Procedure for Functional Check Replacement ComponentsADC113029