c.Flexible hoses or couplings must be used. The dryer vibrates slightly when it runs and this will cause the steam coil connections to crack if they are hard piped to the supply and return mains.
d.
e.Install an inverted bucket steam trap and check valve at least
1)A trap with capacity of 1,200 pounds of condensate per hour at 125 psi is needed for each unit.
f.The supply line and the return line should be insulated. This will save energy and provide for the safety of the operator and maintenance personnel.
g.Water pockets in the supply line, caused by low points, will provide wet steam to the coil possibly causing steam coil damage. ALL horizontal runs of steam supply piping should be pitched
STEAM DAMPER SYSTEM