Emerson SMMC-3 manual Ambient Off Temp. min.34 37F Max.50

Page 10

Pressing UP activates the selected sensor. Pressing DOWN de-activates the selected sensor.

After pressing the UP or DOWN button for <P.Zone3>, the program automatically accepts the selections and advances to the next program level.

Level 4. Ambient Off Temperature Setting

PROGRAM MODE 4.Ambient Off Temp.

The default ambient off temperature is 37°F (3°C).

To move to the next level use the UP or DOWN buttons.

Press the SET button to adjust the ambient off temperature, the temperature above which the SMMC-3 will no longer energize the heating equipment. The minimum and maximum settings possible are noted on the LCD.

4.Ambient Off Temp. min.34 <37°F> Max.50

Pressing UP increases the degree setting. Pressing DOWN decreases the degree setting.

Press the SET button to accept the chosen ambient off temperature and advances to the next program level.

Level 5. Slab Off Temperature Setting

PROGRAM MODE 5.Slab Off Temp.

The default slab off temperature is 50°F (10°C).

To move to the next level use the UP or DOWN buttons. Press the SET button to adjust the slab off temperature, the temperature above which the SMMC-3 will de-energize the in- ground heating equipment. The minimum and maximum settings possible are noted on the LCD.

5.Slab Off Temp. min.41 <50°F> Max.68

Pressing UP increases the degree setting. Pressing DOWN decreases the degree setting.

Press the SET button to accept the chosen slab off temperature and advances to the next program level.

Level 6. Setting the Relay Hold Time

PROGRAM MODE 6.Relay Hold Time

Press the SET button to adjust the relay hold time for the snow melting zones. The relay hold time is the amount of time the snow melting zone remains energized after the moisture sensor is dry. Each of the 3 zones is set independently, in 0.5 hour increments. The minimum and maximum settings possible are noted on the LCD. The relay hold times for all 3 sensors must be stepped through before this operation is complete.

6.Relay Hold Time Z1 min.0 <3.0H> Max.10

6.Relay Hold Time Z2 min.0 <3.0H> Max.10

6.Relay Hold Time Z3 min.0 <3.0H> Max.10

Pressing UP increases the relay hold time. Pressing DOWN decreases the relay hold time.

Press the SET button to accept the chosen relay hold time and advance to the timing for the next zone.

After the hold time for Zone 3 has been set the program automatically returns to programming Level #1 “Temperature Unit Selection”. To exit the programming sequence and return to normal control operation press the BACK button.

Temperature Stand-by

Whenever the ambient air temperature exceeds the ambient off temp, the SMMC-3 goes into a “temperature stand-by” mode, at which time all moisture sensors are de-activated. As soon as the ambient air temperature drops below the ambient off temp, the sensors are reactivated and operation begins as normal.

Outside T = 10°F

Temperature Stand-by

The default relay hold time is 3.0 hours for all zones.

To move to the next level use the UP or DOWN buttons.

PO. Box 726 n TULSA, OK 74101 n TEL 918-627-5530 n FAX 918-641-7336 n www.nelsonheaters.com

GA-2318, R1

Sheet 10 of 15

May 2008

Image 10
Contents SMMC-3 Manual Table of Contents General Information PRE-PROGRAMMED ConfigurationGA-2318, R1 Installation Snow/ice sensor optionsPRE-PROGRAMMED Connections Connection to each sensor is described belowAfter energizing the controller, you should see System CheckBefore you energize the controller, confirm To cycle system and check sensor operationMode 2 Priority Mode 1 IndependentOperation Zone Assignment Time Delay Zone 1 min.0 2.0H Max.10Outside T=-3C A1-A2-A3-P1-P2-P3-M1 Manual OperationMode No.2 2zones 3zones Mode No.1Degree C or F Ambient Off Temp. min.34 37F Max.50 Error!- SMPS-1 Cancel Manual only M1 Error!- SMTS-1 cancelError Messages Troubleshooting Guide Symptoms Probable Cause CorrectionTemperature Aerial Snow Sensor, SMTS-1 Sensor, SMAS-1 SMMC-3 Control Panel Access Cover RemovedGutter Sensor Specifications Sensor Extension Wire SpecificationsLimited Warranty and Liability

SMMC-3 specifications

Emerson SMMC-3 is a cutting-edge controller designed to enhance the efficiency and reliability of industrial automation processes. This smart motor management controller is specifically engineered to optimize the operation of motors and related systems, making it a crucial component in various industrial applications.

One of the standout features of the SMMC-3 is its advanced motor protection capabilities. It provides comprehensive protection against common motor faults such as overloads, phase failures, and short circuits. This ensures that the motors operate within safe parameters, thereby prolonging their lifespan and reducing maintenance costs. The SMMC-3 can be easily configured to meet specific application needs, making it versatile for a wide range of industries.

In addition to protection, the SMMC-3 offers real-time monitoring and diagnostics. It utilizes built-in sensing technologies to continuously monitor key motor parameters, including voltage, current, frequency, and temperature. This data is critical for predictive maintenance, allowing operators to anticipate potential issues before they escalate into costly downtime or equipment failure.

The SMMC-3 supports various communication protocols such as Modbus RTU and TCP, allowing for seamless integration into existing control systems. With its communication capabilities, users can easily access performance data remotely, facilitating better decision-making and resource management.

Another noteworthy characteristic of the SMMC-3 is its user-friendly interface. The device features an intuitive display and menu structure, making it straightforward for operators to configure settings, view performance metrics, and troubleshoot any issues. This ease of use significantly reduces training time and enhances overall operational efficiency.

Moreover, the SMMC-3 employs advanced algorithms and technologies for energy management. It helps in monitoring energy consumption, identifying inefficiencies, and providing recommendations for energy savings. This capability is increasingly important in today’s industrial environment, where reducing energy costs is a top priority.

In summary, Emerson SMMC-3 embodies state-of-the-art technologies and features that elevate motor management in industrial automation. With its robust protection mechanisms, real-time monitoring, versatile communication options, user-friendly design, and energy management capabilities, the SMMC-3 is an invaluable asset for industries striving for operational excellence and sustainability.