Emerson SMMC-3 manual Degree C or F, Mode No.1, Mode No.2 2zones 3zones

Page 9

PROGRAMMING INSTRUCTIONS

The SMMC-3 program has been structured into 6 levels; within each of these levels are further degrees of selection. Each programming step is clearly described on the LCD, and easily adjusted by the “UP”, “DOWN”, and “SET” buttons.

During programming:

All regular operating functions of the SMMC-3 are suspended.

If a button is not pressed for approximately 90 seconds, the program will return to normal operation, saving programming changes made up to the point exited.

Pressing the BACK button results in an exit from the programming sequence, with the changes made up to that point saved.

Resetting to Factory Conditions

When the SMMC-3 is first energized, and during the time the initial LCD display (SMMC Ver. X.X) screen shows push the UP and DOWN buttons simultaneously to access the option to revert to factory set conditions. Use the UP or DOWN button to select “yes” or “no”; the program accepts the selection and returns to normal operation.

To begin programming the SMMC-3 hold the SET button down for 5 seconds. The display will start in program level 1. To move to other levels use the UP or DOWN buttons.

Level 1. Temperature Unit Selection

PROGRAM MODE 1. Degree: °C or °F

The default temperature units setting is °F.

To move to the next level use the UP or DOWN buttons. Press the SET button to select the temperature display units.

1. Degree: °C or °F

<°C >

<°F >

Pressing UP selects Degrees C. Pressing DOWN selects Degrees F.

After pressing the UP or DOWN button, the program automatically accepts the selection and advances to the next program level.

Level 2. Operating Mode Selection

PROGRAM MODE 2.Mode: 1 or 2

The default mode setting is Mode 1.

To move to the next level use the UP or DOWN buttons. Press the SET button to select the operating mode.

2.Mode: 1

or 2

<No.1 >

<No.2 >

Pressing UP selects Mode 1 (Independent). Pressing DOWN selects Mode 2 (Priority).

After pressing the UP button for Mode 1, the program automatically accepts the selection and advances to the next program level.

After pressing the DOWN button for Mode 2, the program automatically accepts the selection and then moves to another input screen, as shown below.

2.Mode No.2 <2zones> <3zones>

Pressing UP selects a 2 Zone system (Zone 1 & 2). Pressing DOWN selects a 3 Zone system (Zone 1, 2 & 3). After pressing the UP or DOWN button, the program automatically accepts the selection and advances to the next program level.

Level 3. Sensor Activation/De-activation

PROGRAM MODE 3.Sensor Activation

The default sensor activation setting is for an aerial (SMAS- 1), or gutter (SMGS-1) sensor, zone 1.

To move to the next level use the UP or DOWN buttons. Press the SET button to begin the process to activate or deactivate sensors. Each of the 3 control zones may have up to 2 individual sensors, for a total of 6 sensors. <A/G.ZoneX> refers to either an SMAS-1 or SMGS-1 sensor, <P.ZoneX>, refers to an SMPS-1 in-ground sensor. The activation/deactivation operation for all 6 sensors must be stepped through before this operation is complete.

3.Sensor Activation Yes <A/G.Zone1> No

3.Sensor Activation Yes <A/G.Zone2> No

3.Sensor Activation Yes <A/G.Zone3> No

3.Sensor Activation Yes <P.Zone1> No

3.Sensor Activation Yes <P.Zone2> No

3.Sensor Activation Yes <P.Zone3> No

PO. Box 726 n TULSA, OK 74101 n TEL 918-627-5530 n FAX 918-641-7336 n www.nelsonheaters.com

GA-2318, R1

Sheet 9 of 15

May 2008

Image 9
Contents SMMC-3 Manual Table of Contents PRE-PROGRAMMED Configuration General InformationGA-2318, R1 Snow/ice sensor options InstallationConnection to each sensor is described below PRE-PROGRAMMED ConnectionsBefore you energize the controller, confirm System CheckAfter energizing the controller, you should see To cycle system and check sensor operationMode 1 Independent Mode 2 PriorityOperation Outside T=-3C A1-A2-A3-P1-P2-P3-M1 Time Delay Zone 1 min.0 2.0H Max.10Zone Assignment Manual OperationMode No.1 Mode No.2 2zones 3zonesDegree C or F Ambient Off Temp. min.34 37F Max.50 Manual only M1 Error!- SMTS-1 cancel Error!- SMPS-1 CancelError Messages Symptoms Probable Cause Correction Troubleshooting GuideSMMC-3 Control Panel Access Cover Removed Temperature Aerial Snow Sensor, SMTS-1 Sensor, SMAS-1Gutter Sensor Sensor Extension Wire Specifications SpecificationsLimited Warranty and Liability

SMMC-3 specifications

Emerson SMMC-3 is a cutting-edge controller designed to enhance the efficiency and reliability of industrial automation processes. This smart motor management controller is specifically engineered to optimize the operation of motors and related systems, making it a crucial component in various industrial applications.

One of the standout features of the SMMC-3 is its advanced motor protection capabilities. It provides comprehensive protection against common motor faults such as overloads, phase failures, and short circuits. This ensures that the motors operate within safe parameters, thereby prolonging their lifespan and reducing maintenance costs. The SMMC-3 can be easily configured to meet specific application needs, making it versatile for a wide range of industries.

In addition to protection, the SMMC-3 offers real-time monitoring and diagnostics. It utilizes built-in sensing technologies to continuously monitor key motor parameters, including voltage, current, frequency, and temperature. This data is critical for predictive maintenance, allowing operators to anticipate potential issues before they escalate into costly downtime or equipment failure.

The SMMC-3 supports various communication protocols such as Modbus RTU and TCP, allowing for seamless integration into existing control systems. With its communication capabilities, users can easily access performance data remotely, facilitating better decision-making and resource management.

Another noteworthy characteristic of the SMMC-3 is its user-friendly interface. The device features an intuitive display and menu structure, making it straightforward for operators to configure settings, view performance metrics, and troubleshoot any issues. This ease of use significantly reduces training time and enhances overall operational efficiency.

Moreover, the SMMC-3 employs advanced algorithms and technologies for energy management. It helps in monitoring energy consumption, identifying inefficiencies, and providing recommendations for energy savings. This capability is increasingly important in today’s industrial environment, where reducing energy costs is a top priority.

In summary, Emerson SMMC-3 embodies state-of-the-art technologies and features that elevate motor management in industrial automation. With its robust protection mechanisms, real-time monitoring, versatile communication options, user-friendly design, and energy management capabilities, the SMMC-3 is an invaluable asset for industries striving for operational excellence and sustainability.