Installation |
|
|
|
|
|
| ||
Cabling Guidelines | Table 1 : Voltage Drop Per Foot of DC Cable |
| ||||||
Follow these guidelines and refer to Table 1 : Voltage Drop Per |
| |||||||
|
|
|
|
|
| |||
| Inverter |
|
|
|
| |||
Foot of DC Cable on page 10 to determine battery cable lengths. |
|
|
|
|
| |||
| Output (W) | 600 | 1000 | 1500 | 3000 | |||
• | Use 4 AWG copper (90 ºC insulation rating) as the smallest |
| Current (A) | 60 | 100 | 150 | 300 | |
| battery cable size. This will minimize the voltage drop between |
|
|
|
|
|
| |
| Wire | Resistance |
|
|
|
| ||
| the battery and the inverter. If the cables cause an excessive | Size | (ohms/ft) |
| Voltage Drop per Foot |
| ||
| voltage drop, the inverter may shut down when drawing higher | (AWG) | @ 25 °C |
|
| |||
| currents because the voltage at the inverter input drops below | 4 | 0.000253 | 0.0152 | 0.0253 | 0.0380 | 0.0759 | |
| 3 | 0.000201 | 0.0121 | 0.0201 | 0.0302 | 0.0603 | ||
| 10.5 volts. | |||||||
| 2 | 0.000159 | 0.0096 | 0.0159 | 0.0239 | 0.0477 | ||
• | Keep all cables as short as possible, and ensure that each cable | |||||||
1 | 0.000126 | 0.0076 | 0.0126 | 0.0189 | 0.0378 | |||
| between the inverter and the battery is no longer than 6 feet | |||||||
| 0 | 0.000100 | 0.0060 | 0.0100 | 0.0150 | 0.0300 | ||
| (1.8 m). | |||||||
| 2/0 | 0.000079 | 0.0048 | 0.0079 | 0.0119 | 0.0237 | ||
• | Have all wires and cables terminated with correct and | |||||||
3/0 | 0.000063 | 0.0038 | 0.0063 | 0.0095 | 0.0189 | |||
|
|
|
|
|
|
| ||
| 4/0 | 0.000050 | 0.0030 | 0.0050 | 0.0075 | 0.0150 | ||
| crimped at the place of purchase. |
|
|
|
|
|
| |
| Note: Xantrex recommends a size 0 cable with a maximum cable | |||||||
• | Do not use aluminum. It has about 1/3 more resistance than | |||||||
length of 6 feet (1.8 m). |
|
|
| |||||
| copper cable of the same size, and it is difficult to make good, |
|
|
| ||||
| For example: |
|
|
|
| |||
|
|
|
|
|
Note: Voltage Drop per foot = Current value × Resistance value
So for a 600 W inverter output with a DC cable of size 0, multiply the maximum current of 60 A with 0.000100. The result is 0.00600 voltage drop per feet. If the cable is 6 feet long, the total voltage drop is 0.00600 × 6 ( × 2) = 0.072. (Cable length multiplied by 2.)
So for a battery operating at 12.6 V at battery terminal the voltage at the inverter terminal drops to 12.53 V.
10 | Xantrex PROwatt™ SW Sine Wave Inverter Owner’s Guide |