Troubleshooting
Condition | Possible Cause | Solution |
|
|
|
E 1 0 | Short circuit | Check the AC |
No output voltage. |
| wiring for a short |
|
| circuit. |
| Very heavy load | Remove the load. |
| Output circuit | Turn the unit off. |
| overheat | Let the unit cool |
|
| down, check the fan |
|
| for any obstructions |
|
| and clear it, or |
|
| reduce the load. |
|
| Turn the unit back |
|
| on. |
|
|
|
Condition | Possible Cause | Solution |
|
|
|
No output voltage; | The unit is off. | Turn the inverter on. |
no voltage | No power to the | Check wiring to the |
indication. | inverter. | inverter. |
| Inverter fuse open. | Have a qualified |
| Reverse DC polarity. | service technician |
|
| check and replace |
|
| the fuse if necessary. |
|
| Have a qualified |
|
| service technician |
|
| check and replace |
|
| the fuse, making |
|
| sure to observe |
|
| correct polarity. |
|
|
|
The unit is on and | The GFCI device | Reset the GFCI. See |
running but there is | tripped. | page 16 for |
no AC output. |
| instructions. |
|
|
|
20 | Xantrex PROwatt™ SW Sine Wave Inverter Owner’s Guide |