Troubleshooting
Troubleshooting Reference
WARNING: Electrical shock and burn hazard
Do not disassemble the inverter. It does not contain any
Some of the following Solutions should be referred to a qualified electrician or electrical service person.
Table | Troubleshooting Reference |
|
| ||
|
|
|
|
| |
| Error/Warning |
|
|
| |
# | Code on Display | Problem | Possible Cause | Solution | |
|
|
|
|
| |
1 | E01: Flashing | Inverter is in | E05 warning code is | See solution under error # 5 in | |
| Fault LED: | undervoltage | ignored. (See possible | this table. | |
| Flashing |
| shutdown. | causes under error # “3” |
|
| Alarm: Beeping |
| in this table). |
| |
|
|
|
|
| |
2 | E02: Flashing | Inverter is in | High input voltage | Make sure the inverter is | |
| Fault LED: | overvoltage |
| connected to a 12 V battery. | |
| Flashing |
| shutdown. |
| Check the voltage regulation |
| Alarm: Beeping |
|
| ||
|
|
|
|
| of the charging system. |
|
|
|
|
| |
3 | E03: Flashing | Inverter is in | E06 warning code is | See solution under error # 6 in | |
| Fault LED: | overload shutdown. | ignored. (See possible | this table. | |
| Flashing |
|
| causes under error # 8 in |
|
| Alarm: Beeping |
| this table). |
| |
|
|
| Inverter is in short | Inverter has short- | Disconnect DC power to the |
|
|
| circuit shutdown. | circuited. | inverter. Have a qualified |
|
|
|
|
| electrician check the AC |
|
|
|
|
| output connections, wiring, |
|
|
|
|
| and appliances for indications |
|
|
|
|
| of short circuits. |
|
|
|
|
|
|