U.S. ELECTRICAL MOTORS INSTALLATION AND MAINTENANCE

Storage

(C)Insulation resistance readings must not drop below the value indicated by the following formula:

Rm = Kv + 1

Rm = minimum insulation, in megohms, at 40°C

Kv = rated motor voltage in kilovolts

(D)Dielectric Absorption Ratio:

In addition to the individual test reading, a dielectric absorption ratio may be required. The dielectric absorption ratio is obtained by taking megohmmeter readings at a one minute and ten minute interval or when hand powered megohmmeters are used, at a thirty second and sixty second interval. The voltage should be the same as outlined in Part A of this procedure.

The ratio is obtained by dividing the second reading by the first reading and is based on a good insulation system increasing its resistance when subjected to a test voltage for a period of time.

The ratios are as follows:

10 minute : 1 minute

60 second : 30 second

Dangerous

=

less than 1.0

Poor

=

less than 1.1

Poor

=

1.0 to 1.4

Questionable

=

1.1 to 1.24

Questionable

=

1.5 to 1.9

Fair

=

1.25 to 1.3

Fair

=

2.0 to 2.9

Good

=

1.4 to 1.6

Good

=

3.0 to 4.0

Excellent

=

Over to 1.6

Excellent

=

Over 4.0

 

 

 

If a low insulation resistance reading is obtained in either the individual test or dielectric absorption ratio test, thoroughly clean and dry the windings. Recheck insulation resistance and dielectric absorption ratio.

NOTE: Slightly lower dielectric absorption ratios may be acceptable when high initial insulation resistance readings are obtained (1,000 + megohms). Refer any questions to U.S.E.M. Product Service Department.

For additional information on insulation testing, refer to IEEE Transaction No. 43.

4.Start-up Preparations after Storage.

(A)Motor should be thoroughly inspected and cleaned to restore to an "As Shipped" condition.

(B)If motor has been in storage for less than 6 months, remove grease drain plugs at each end of the motor. Remove a small quantity of grease with a scavenger and replace drain plugs. If any moisture or contamination is evident in the grease, it must be completely changed by disassembling the unit and repacking per Section XI "Lubrication".

(C)If motor has been in storage for 6 months or more, grease must be completely changed by disassembling the unit and repacking per Section XI "Lubrication".

(D)The winding must be tested to obtain insulation resistance and dielectric absorption ratio as described in Part 3 of this section.

(E)If storage has exceeded one year, the U.S.E.M. Quality Assurance Department must be contacted prior to equipment start-up.

4

Image 9
Contents Titan Page Safety First SafetyTable of Contents Page II. Handling ShipmentIII. Storage StorageStorage Storage Installation Location Installation Location FoundationFoundation GroutingInitial Installation Initial InstallationFlexible Couplings Angular MisalignmentParallel Alignment Operated uncoupled from driven equipment NO-LOAD Vibration Limits Normal OperationVelocity, Inches per second Speed, RPMDoweling Normal OperationVIII. Doweling Disassembly Reassembly IX. DisassemblyReassembly Dowel PIN Holes XI. Lubrication LubricationManufacturer Description Electrical Motors XII. Renewal Parts and Service Renewal Parts ServiceRecommended Fastener Torque Values Fastener Size Torque* Ft.- LbsXIII. Cutawaydrawings Cutaway DrawingsXIV Troubleshooting Possible Cause Correction TroubleshootingTrouble Possible Cause Correction Record Installation Record

986269, LARGE AC ELECTRIC MOTORS specifications

Emerson Large AC Electric Motors, specifically model 986269, exemplify cutting-edge technology and exceptional design, catering to the diverse needs of industrial applications. These motors are engineered for reliability, efficiency, and performance, making them suitable for various sectors, including manufacturing, mining, and oil and gas.

One of the standout features of the Emerson 986269 motor is its robust construction. Built to withstand harsh operational environments, this motor has a durable housing that protects it from external contaminants such as dust, moisture, and chemicals, thereby prolonging its lifespan. The design promotes efficient heat dissipation, which minimizes overheating risks and enhances both performance and reliability.

Energy efficiency is a critical aspect of the Emerson 986269 AC electric motor. Utilizing advanced design methodologies, the motor offers high efficiency ratings, which translates into lower operational costs and reduced carbon footprints. It meets or exceeds the latest efficiency standards, making it an eco-friendly choice while ensuring optimal performance in various applications.

Another significant feature is its versatility. The Emerson 986269 motor is available in various sizes and configurations, making it suitable for different tasks and load requirements. Its adaptability allows seamless integration into existing systems, making it a valuable asset for businesses looking to upgrade their machinery without extensive modifications.

The motor employs state-of-the-art technologies such as premium-quality bearings and insulation systems, contributing to its quiet operation and minimal maintenance requirements. This means reduced downtime and increased productivity, both vital for maintaining competitive advantages in today's fast-paced industrial landscape.

Moreover, Emerson's commitment to safety is reflected in the design of the 986269 motor. It is equipped with advanced thermal protection features and complies with international safety standards, ensuring secure operation even in challenging conditions.

In conclusion, the Emerson Large AC Electric Motor 986269 sets the benchmark for performance, reliability, and efficiency in industrial applications. With its robust construction, energy-efficient design, and advanced technologies, it is an investment that promises long-term operational benefits and peace of mind for users. Whether for heavy-duty tasks or general industrial use, this motor remains a top choice for companies aiming to enhance their operational efficiency and productivity.