INSTALLATION
Venting Installation (Con.)
Electrical Gookup and Remote Reeiver Diagram
Gas Supply Testing
7
INSTALLATION
Continued
If an offset is necessary in the attic to avoid obstruction, it is important to support the vent pipe every 3 ft. to avoid excessive stress on the elbows and possible separation (see Figure 8, page 7).
Clearances must be maintained between the roof and the ter- mination. Refer to chart below.
Roof Pitch | Minimum Height Above Roof |
|
|
Flat - 7/12 | 1 ft. (30.48 cm) |
7/12 - 8/12 | 1 1/2 ft. (45.72 cm) |
8/12 - 9/12 | 2 ft (60.96 cm) |
9/12 - 10/12 | 2 1/2 ft (76.20 cm) |
10/12 - 11/12 | 4 ft (121.92 cm) |
11/12 - 14/12 | 5 ft (152.40 cm) |
14/12 - 16/12 | 6 ft (182.88 cm) |
16/12 - 18/12 | 7 ft (213.36 cm) |
18/12 - 20/12 | 7 1/2 ft (228.60 cm) |
20/12 - 21/12 | 8 ft (243.84 cm) |
|
|
Outlet Box
Figure 9 - Duplex Outlet
|
| H |
|
| T |
| PI LOT | P |
| ON | |
| TO | T |
| L |
|
| IP |
|
| F | H |
| FO | |
|
| T |
| T | P |
| T | |
| H |
|
| P |
|
| T |
|
Convertible | H |
|
T |
| |
| P |
|
| T |
|
Gas Valve
REMOTE | OFF |
|
|
| ON |
Remote Control
Receiver
Figure 10 - Remote Control Receiver
Roof Flashing
Wall Strap
45° Elbows
Ceiling Firestop
Figure 8 - Vertical Termination with Offset and Wall Strap
ELECTRICAL HOOKUP AND REMOTE RECEIVER DIAGRAM
An outlet box with two receptacles (see Figure 9) has been supplied for your convenience and is located inside on the lower right side of the fireplace.
The remote control receiver is factory wired and connected to the convertible gas valve as shown in Figure 10.
GAS SUPPLY TESTING
NOTICE: This section is intended as a guide for qualified technicians installing gas to the appliance.
WARNING: Do not connect appliance before pres- sure testing gas piping. Damage to gas valve may result and an unsafe condition may be created.
The appliance and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 1/2 psig (3.5 kPa).
The appliance must be isolated from the gas supply piping system by closing its individual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 1/2 psig (3.5 kPa).
The gas control valve is secured underneath the firebox. Two 1/8" ports are provided on the gas control valve for pressure test gauge connections (see Figure 11).
|
| Pilot Adjustment |
| To Pilot Burner | ||
|
|
|
| |||
ON/OFF |
|
|
| ILOT |
| Pilot Gas |
Knob |
|
|
|
| Line Do | |
|
|
| P |
| ||
| N |
| 16AI |
| ||
|
|
|
|
| ||
|
| O |
|
| Not Kink | |
| P |
|
|
| ||
| O | T |
|
| TH |
|
|
|
| 7 |
| ||
| I |
|
| |||
| L |
|
|
|
| |
|
|
| L | I |
| To Main |
|
| FFO | O | H | TP | |
|
|
| ||||
|
| E | A |
| TPTH | Burner |
Inlet |
|
|
|
| ||
|
|
| Flame Adjustment Knob | |||
Pressure |
|
|
| |||
Outlet Pressure |
|
| ||||
|
|
| ||||
Figure 11 - Gas Control Valve |
|
|
For..com