Desa CGCF26TNA Checking GAS Connections, Pressure Testing Gas Supply Piping System

Page 13

OWNER’S MANUAL

INSTALLATION

Continued

CHECKING GAS

CONNECTIONS

WARNING: Test all gas pip- ing and connections for leaks after installing or servicing. Cor- rect all leaks at once.

WARNING: Never use an open flame to check for a leak. Apply a mixture of liquid soap and water to all joints. Bubbles forming show a leak. Correct all leaks at once.

Pressure Testing Gas Supply Piping System

Test Pressures In Excess Of 1/2 PSIG

1.

Disconnect fireplace and its individual

 

manual shutoff valve from gas supply

 

piping system. Pressures in excess of

 

1/2 psig will damage fireplace regulator.

2.

Cap off open end of gas pipe where

 

manual shutoff valve was connected.

3.

Pressurize supply piping system by

 

either using compressed air or open-

Test Pressures Equal To or Less Than 1/2 PSIG

1.Close manual shutoff valve (see Figure 19).

2.Pressurize supply piping system by either using compressed air or open- ing main gas valve located on or near gas meter.

3.Check all joints from gas meter to manual shutoff valve (see Figure 20). Apply mixture of liquid soap and wa- ter to gas joints. Bubbles forming show a leak.

4.Correct all leaks at once.

Manual

ON

Open

Shutoff

POSITI

 

Valve

 

O

Closed

POS

Figure 19 - Manual Shutoff Valve

Pressure Testing Fireplace Gas Connections

1.Open manual shutoff valve (see Fig- ure 19).

2.Open main gas valve located on or near gas meter.

3.Make sure control knob of fireplace is in the OFF position.

4.Check all joints from manual shutoff valve to thermostat gas valve (see Fig- ure 20). Apply mixture of liquid soap and water to gas joints. Bubbles form- ing show a leak.

5.Correct all leaks at once.

6.Light fireplace (see Operating Fire- place, pages 14 and 15). Check all other internal joints for leaks.

7.Turn off fireplace (see To Turn Off Gas to Appliance, page 15).

8.Replace front panel.

 

ing main gas valve located on or near

 

gas meter.

4.

Check all joints of gas supply piping

 

system. Apply mixture of liquid soap

 

and water to gas joints. Bubbles form-

 

ing show a leak.

5.

Correct all leaks at once.

6.

Reconnect heater and manual shutoff

 

valve to gas supply. Check reconnected

 

fittings for leaks.

 

Manual

 

Shutoff

Gas Meter

Valve

Figure 20 - Checking Gas Joints

104277

13

Image 13
Contents What to do if YOU Smell GAS OWNER’S Operation and Installation ManualVENT-FREE Natural GAS Compact Fireplace Safety InformationProduct Identification Product FeaturesLocal Codes UnpackingInstalling Log AssemblyAssembling Fireplace Assembling HoodProviding Adequate Ventilation AIR for Combustion and VentilationUnusually Tight Construction Confined and Unconfined SpaceDetermining FRESH-AIR Flow for Fireplace Location AIR for Combustion VentilationDetermining if You Have a Confined or Unconfined Space Ventilation Air From Inside Building Ventilation AIRVentilation Air From Outdoors Installation Items InstallationCheck GAS Type Locating FireplaceRough Opening for Installing in Corner BUILT-IN Fireplace InstallationOptional Mantel Installation Mantel Clearances for BUILT-IN InstallationAttaching Wood Base to Solid Floor Connecting to GAS SupplyInstallation Items Needed Connecting Fireplace to GAS SupplyPressure Testing Fireplace Gas Connections Pressure Testing Gas Supply Piping SystemChecking GAS Connections Operating Fireplace For Your Safety Read Before LightingLighting Instructions Inspecting Burner Observed Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement at Replacement Parts Cleaning and MaintenanceService Hints CGCF26TNA Illustrated Parts BreakdownKEY Description QTY Parts ListManual Shutoff Valve GA5010 AccessoriesBrass Trim KIT GA6095 Thermostatically Controlled Blower KIT GA3450TTechnical Service SpecificationsParts Centrals FBDLimited Warranty VENT-FREE Natural GAS Compact Fireplace Warranty Information