Desa LFP33NR AIR for Combustion Ventilation, Determining FRESH-AIR Flow for Fireplace Location

Page 5

OWNER’S MANUAL

AIR FOR

COMBUSTION AND

VENTILATION

Continued

DETERMINING FRESH-AIR FLOW FOR FIREPLACE LOCATION

Determining if You Have a Confined or Unconfined Space

Use this work sheet to determine if you have a confined or unconfined space.

Space: Includes the room in which you will install fireplace plus any adjoining rooms with doorless passageways or ventilation grills between the rooms.

1.Determine the volume of the space (length x width x height).

Length x Width x Height = _________________ cu. ft. (volume of space)

Example: Space size 22 ft. (length) x 18 ft. (width) x 8 ft. (ceiling height) = 3168 cu. ft. (volume of space)

If additional ventilation to adjoining room is supplied with grills or openings, add the volume of these rooms to the total volume of the space.

2.Divide the space volume by 50 cubic feet to determine the maximum Btu/Hr the space can support.

_________________ (volume of space) ÷ 50 cu. ft. = (Maximum Btu/Hr the space can support)

Example: 3168 cu. ft. (volume of space) ÷ 50 cu. ft. = 63.3 or 63,300 (maximum Btu/Hr the space can support)

3.Add the Btu/Hr of all fuel burning appliances in the space.

Vent-free fireplace

 

___________________ Btu/Hr

 

 

 

 

Gas water heater*

 

___________________ Btu/Hr

 

 

 

 

Gas furnace

 

___________________ Btu/Hr

Example:

 

 

 

Vented gas heater

 

___________________ Btu/Hr

Gas water heater

 

40,000

Btu/Hr

Gas fireplace logs

 

___________________ Btu/Hr

Vent-free fireplace

+

33,000

Btu/Hr

Other gas appliances*

+

___________________ Btu/Hr

Total

=

73,000

Btu/Hr

Total

=

___________________ Btu/Hr

 

 

 

 

*Do not include direct-vent gas appliances. Direct-vent draws combustion air from the outdoors and vents to the outdoors.

4.Compare the maximum Btu/Hr the space can support with the actual amount of Btu/Hr used.

_________________ Btu/Hr (maximum the space can support)

_________________ Btu/Hr (actual amount of Btu/Hr used)

Example: 63,300 Btu/Hr (maximum the space can support) 73,000 Btu/Hr (actual amount of Btu/Hr used)

The space in the above example is a confined space because the actual Btu/Hr used is more than the maximum Btu/Hr the space can support. You must provide additional fresh air. Your options are as follows:

A.Rework work sheet, adding the space of an adjoining room. If the extra space provides an unconfined space, remove door to adjoin- ing room or add ventilation grills between rooms. See Ventilation Air from Inside Building, page 6.

B.Vent room directly to the outdoors. See Ventilation Air from Outdoors, page 6.

C.Install a lower Btu/Hr fireplace, if lower Btu/Hr size makes room unconfined.

If the actual Btu/Hr used is less than the maximum Btu/Hr the space can support, the space is an unconfined space. You will need no additional fresh air ventilation.

WARNING: If the area in which the heater may be operated is smaller than that defined as an unconfined space or if the building is of unusually tight construction, provide adequate combustion and ventilation air by one of the methods described in the National Fuel Gas Code, ANS Z223.1, 1992, Section 5.3 or applicable local codes.

Continued

104887

5

Image 5
Contents What to do if YOU Smell GAS Unvented VENT-FREE Natural GAS FireplaceLFP33NR Unvented Natural GAS Fireplace Safety InformationProduct Identification Remote Control AccessoriesLocal Codes UnpackingAIR for Combustion and Ventilation Product FeaturesDetermining if You Have a Confined or Unconfined Space AIR for Combustion VentilationDetermining FRESH-AIR Flow for Fireplace Location Ventilation Air From Outdoors Ventilation AIRVentilation Air From Inside Building Optional Blower Accessory InstallationCheck GAS Type Electrical HookupMinimum Wall and Ceiling Clearances see Figure Conventional Fireplace InstallationLocation of Nailing Flanges BUILT-IN Fireplace InstallationInstallation Items Needed Installing GAS Piping to Fireplace LocationMantel Clearances for Built-In Installation Removing Log Base Assembly From Fireplace Connecting Fireplace to GAS SupplyChecking GAS Connections Pressure Testing Gas Supply Piping SystemPressure Testing Fireplace Gas Connections Installing Screen Installing LogsInstalling Batteries for RM4 Optional Wireless HAND- Held Remote Control Accessory RM4Installing Remote Receiver Unit Installing Batteries in Hand-Held Remote Control UnitInstalling Battery in Hand-Held Remote Control Unit Installing Batteries for Ghrc and Ghrct SeriesInstalling Battery in Receiver Lighting Instructions For Your Safety Read Before LightingOperating Fireplace To Turn OFF GAS To Appliance Manual Lighting ProcedureOptional Remote Operation Optional Blower OperationInspecting Burners Cleaning and MaintenanceObserved Problem Possible Cause Remedy TroubleshootingMaintenance, Gas leak. See Warning statement Technical Service Specifications Wiring DiagramService Hints Parts Under Warranty Replacement PartsParts not Under Warranty Parts CentralCorner Mantel AccessoriesGMC11F Series Walnut Finished Hardwood Veneer GMC13F Series Medium Stained Oak VeneerReceiver and HAND- Held Remote Control KIT Cghrc Series HAND-HELD Remote Control RM4Blower Accessories Manual Shutoff Valve GA5010Remote Ready Model LFP33NR Illustrated Parts BreakdownKEY Part Number Description QTY Parts ListFireplace LFP33NR Parts List Warranty Information