Technical Data
PWW 4000 series |
|
|
|
|
|
|
|
|
|
|
Type |
| 4030 - 3 | 4030 - 4 | 4050 - 3 | 4050 - 4 | |||||
|
|
|
|
|
| |||||
Electrical connection | V | 400 / 3~ N | 400 / 3~ N | 400 / 3~ N | 400 / 3~ N | |||||
Frequency | Hz | 50 | 50 | 50 | 50 | |||||
Power consumption | kW | 0.13 | / 0.10 | 0.13 | / 0.10 | 0.26 | / 0.18 | 0.26 | / | 0.18 |
Rated current | A | 0.26 | / 0.16 | 0.26 | / 0.16 | 0.52 | / 0.29 | 0.52 | / | 0.29 |
Speed | U/min | 1340 | / 1040 | 1340 | / 1040 | 1360 | / 1020 | 1360 | / | 1020 |
Air capacity | m³/h | 2050 | / 1640 | 1850 | / 1500 | 3400 | / 2870 | 3150 | / | 2770 |
Sound pressure level 1) | dB(A) | 53 | / 48 | 55 | / 49 | 55 | / 51 | 58 | / | 54 |
Heating medium connection | inch | R1" | R1¼" | R1" | R1¼" | |||||
|
|
|
|
|
| |||||
Heating medium |
| Pump warm water or pump hot water up to max. 130 °C | ||||||||
Operating pressure | bar | 16 |
|
|
| |||||
16 | 16 | 16 | ||||||||
Weight | kg | 26 | 27 | 34 | 36 | |||||
|
|
|
|
|
|
|
|
| ||
1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s |
|
|
|
| ||||||
|
|
|
|
|
|
|
|
|
|
|
PWW 4000 series |
|
|
|
|
|
|
|
|
|
|
Type |
| 4080 - 3 | 4080 - 4 | 4100 - 3 | 4100 - 4 | |||||
|
|
|
|
|
| |||||
Electrical connection | V | 400 / 3~ N | 400 / 3~ N | 400 / 3~ N | 400 / 3~ N | |||||
Frequency | Hz | 50 | 50 | 50 | 50 | |||||
Power consumption | kW | 0.42 | / 0.28 | 0.42 | / 0.28 | 0.76 | / 0.47 | 0.76 | / | 0.47 |
Rated current | A | 0.76 | / 0.46 | 0.76 | / 0.46 | 1.50 | / 0.81 | 1.50 | / | 0.81 |
Speed | U/min | 880 | / 670 | 880 | / 670 | 870 | / 650 | 870 | / | 650 |
Air capacity | m³/h | 5400 | / 4300 | 4730 | / 4700 | 8250 | / 6620 | 7670 | / | 6180 |
Sound pressure level 1) | dB(A) | 55 | / 49 | 55 | / 49 | 58 | / 54 | 59 | / | 55 |
Heating medium connection | inch | R1¼" | R1¼" | R1½" | R1½" | |||||
|
|
|
|
|
| |||||
Heating medium |
| Pump warm water or pump hot water up to max. 130 °C | ||||||||
Operating pressure | bar | 16 |
|
|
| |||||
16 | 16 | 16 | ||||||||
Weight | kg | 47 | 51 | 60 | 68 | |||||
|
|
|
|
|
|
|
|
|
|
|
1) Measurement at intervals of 5 m, measuring room volume 800 m³, average reverberation time 1.4 s